Mechanical Installation
14 / 79
G
M10 spring washer
6
For mounting bracket.
H
M12 nut
6
For AC terminal block
I
M12 flat gasket
6
For AC terminal block
J
M12 spring washer
6
For AC terminal block
K
M12 big flat gasket
6
For AC terminal
L
M6x18 screw with plastic
flat washer
1
Spare for front cover
M
Handle
2
Carry the inverter.
N
6-pin connector plug
1
For RS485 comm.
O
LINKIT
1
For communication.
Table 3-1 Accessory list
IMPORTANT!
The items on the delivery list above are for the standard configuration.
The accessories provided may vary if optional parts are purchased.
Installation Precautions
Check that the product environmental specifications (protection degree,
operating temperature range, humidity and altitude, etc.) meet the
requirements of the specific project location.
Make sure that the power grid voltage is within the normal range of the
Grid Code chosen.
Ensure that you have been authorized by the local electricity supply
authority to connect to the grid.
Installation personnel must be qualified electricians or those who have
received professional training.
Wear and use proper PPE (personal protective equipment) during
installation.
Sufficient space must be provided to allow the inverter cooling system
to operate normally.
Install the inverter away from flammable and explosive substances.
Make sure the installation condition doesn’t exceed the temperature
limits specified for the inverter, to prevent undesirable power loss.
Do not install the inverter near an electromagnetic source which can
compromise the normal operation of electronic equipment
The PV Array is not grounded.
The conduits entries meet the following:
-
ALL Conduit Entries must use water-tight fittings.
-
ALL Conduit Entries should use sealant around wires inside wire-
compartment to prevent moisture ingress.
-
ALL Conduit Fittings should be metal to contain any thermal event in
the wire-compartment – cause by moisture ingress.
For detailed specification ranges and limits, see Chapter 9, Technical Data.