General Introduction
12 / 79
Smart Inverter Functions and Default Activation
Function
IEEE1547-2018 Rule 21
ISO-NE
Anti-islanding
Enabled
Enabled
Enabled
Low/High Voltage Ride-through Enabled
Enabled
Enabled
Low/High Frequency Ride-
through
Enabled
Enabled
Enabled
Dynamic Volt/VAR Operation
Enabled
Enabled
Enabled
Ramp Rate
Enabled
Enabled
Enabled
Fixed Power Factor
Disabled
Disabled
Disabled
Reconnect by “Soft-Start”
Enabled
Enabled
Enabled
Frequency-Watt
Enabled
Enabled
Enabled
Volt/Watt
Enabled
Enabled
Enabled
Table 2-1 Smart inverter functions and default activation
Anti-islanding Detection
The inverter includes Anti-Islanding detection as required by UL1741/IEEE1547. It
will continuously make bi-directional perturbations to the frequency of the output
current by injecting a small amount of reactive power in order to detect a possible
islanding condition. If the grid is stable, these small perturbations will have
negligible effects on the system voltage frequency. However, in an islanded
condition the changes in reactive power will force the frequency of the system
voltage to deviate significantly, which will trigger the inverter to cease operation
and disconnect from the grid.
Surge Suppression
Standard Waveform Peak Values
Surge Category
Ring Wave*
Combination Wave**
B
6kV/0.5kA
6kV/3kA
Table 2-2 Standard Waveform Peak Values
Notes:
* stands for 0.5μs - 100 kHz Ring Wave
** stands for 1.2/50μs - 8/20μs Combination Wave