66
Table 5-1 The Protection Parameters (Continued)
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
Grid Over Frequency Protection (Table 5.7 (19-21))
GridF.Max1
Threshold Level 1 Max.
grid frequency
{60, 66}
{60.5}
{60.5}
{61.2}
FMaxTripTime1(S
)
Trip time of Level 1 Max.
grid frequency
{0, 655}
{2}
{299.50}
{300.0}
GridF.Max2
Threshold Level 2 Max.
grid frequency
{60, 66}
{62}
{62}
{62}
FMaxTripTime2(S
)
Trip time of Level 2 Max.
grid frequency
{0, 655}}
{0.16}
{0.16}
{0.16}
GridF.Max3
Threshold Level 3 Max.
grid frequency
{60, 66}
{62}
{62}
{62}
FMaxTripTime3(S
)
Trip time of Level 3 Max.
grid frequency
{0, 655}
{0.16}
{0.16}
{0.16}
Grid Low Frequency Protection (Table 5.7 (22-24))
GridF.Min1
Threshold Level 1 Min.
grid frequency
{54, 60}
{59.5}
{58.5}
{58.5}
FrqMinTripTime1(S
)
Trip time of Level 1 Min.
grid frequency
{0, 655}
{2}
{299.50}
{300.00}
GridF.Min2
Threshold Level 2 Min.
grid frequency
{54, 60}
{57}
{57}
{56.5}
FMinTripTime2(S
)
Trip time of Level 2 Min.
grid frequency
{0, 655}
{0.16}
{0.16}
{0.16}
GridF.Min3
Threshold Level 3 Min.
grid frequency
{54, 60}
{57}
{57}
{56.5}
FMinTripTime3(S
)
Trip time of Level 3 Min.
grid frequency
{0, 655}
{0.16}
{0.16}
{0.16}
FMaxRcov(Hz)
Recovery Max threshold
grid Frequency protection
{54, 66}
{60.3}
{60.4}
{60.1}
FMinRcov(Hz)
Recovery Min threshold.
grid Frequency protection
{54, 60}
{59.8}
{58.6}
{59.5}
FRcovT(S)
Recovery time of grid
frequency protection
{0, 655}
{300}
{300}
{300}
Содержание SCH Series
Страница 2: ......
Страница 4: ......
Страница 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Страница 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Страница 58: ...54 Figure 4 1 System setting ...
Страница 60: ...56 Figure 4 2 Normal Operation Status Summary Screen SWIPE TO CHANGE MENUS SEE MENUS IN SECTION 5 4 ...
Страница 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...
Страница 89: ...85 Firmware released to Cloud Firmware downloaded in Pocket INTERNET CONNECTION WiFi to Inverter ...
Страница 90: ...86 WiFi to Inverter ...
Страница 92: ...88 ...
Страница 93: ...89 5 5 History There are 2 submenus in the History menu Alarm and Running Status ...