69
Table 5-2 Active Power Derating Setup
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
OVER-VOLTAGE DERATE (Table 5-7 (34) to Enable)
OVDeratStart
The trigger Voltage of
Overvoltage derating {100%, 135%}
{110%}
{110%}
{110%}
OVDeratRate
Rate of Overvoltage
derate
{0%, 100%}
{0%}
{0%}
{0%}
OvrVoltFilterT(s)
The filtering time of Over
Voltage derating
{1 ,90}
{60}
{60}
{60}
OVER-FREQUENCY DERATE (Table 5-7 (29) to Enable)
OFDeratStart(Hz)
The trigger frequency of
Over Frequency derating
{60, 72}
{60.5}
{60.1}
{60.1}
OFDeratStop(Hz)
The end frequency of
Over frequency derating
{60, 72}
{61.4}
{62}
{62}
OFDeratRate(P%/Hz)
The rate of Over
frequency derating
{0.01, 100}
{0.16}
{30}
{30}
OFDeratRcovFre(Hz)
The recovery frequency
of Over Frequency
derating
{58.8, 66}
{60}
{59.90}
{59.90}
OFDeratRcovT(s)
The recovery time of
Over Frequency derating
{0,1200}
{60}
{600}
{600}
OptOverVolPrct
The Value of Operating
overvoltage protect {100%, 135%}
{120%}
{120%}
{120%}
Содержание SCH Series
Страница 2: ......
Страница 4: ......
Страница 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Страница 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Страница 58: ...54 Figure 4 1 System setting ...
Страница 60: ...56 Figure 4 2 Normal Operation Status Summary Screen SWIPE TO CHANGE MENUS SEE MENUS IN SECTION 5 4 ...
Страница 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...
Страница 89: ...85 Firmware released to Cloud Firmware downloaded in Pocket INTERNET CONNECTION WiFi to Inverter ...
Страница 90: ...86 WiFi to Inverter ...
Страница 92: ...88 ...
Страница 93: ...89 5 5 History There are 2 submenus in the History menu Alarm and Running Status ...