107
INSTRUCTION:
The PF (P) Curve function is only available for IEEE-1547 and Rule21
grid standards.
3. Q(U) Curve
:
Q(U) curve mode. Using the curves to set the reactive
power setpoints (See Figure 6-16). The reactive power compensation
changes according to the grid voltage. These functions are only
available for IEEE-1547 and Rule21 grid standards.
Figure 6-16 Q(U) Curve Mode
INSTRUCTION:
The Q(U) curve function is available for IEEE-1547 and Rule21 grid
standards.
Table 6- lists the parameters for PF Set and Q(U) Curve modes. Press
ENT
to start the modes after the parameters are set.
Capacitive
Q
(%)
_
+
Inductive
(
QuCurveU
2
i
,
QuCurveQ
2
i
)
U
(
V
)
(
QuCurveU
1
i
,
QuCurveQ
1
i
)
(
QuCurveU
1
,
QuCurveQ
1
)
(
QuCurveU
2
,
QuCurveQ
2
)