102
OvrFrqRecoveryT
(s)
The recovery time of
OverFrequency
derating
0
60
1200
0
20
1200
0
90
1200
OvrFrqDeratingM
ode
Over frequency
derating
enable/disable
0: Disable
1: Enable
0
0
1
0
0
1
0
0
1
CtrMode
The control mode of
active power
0: Disable dispatch
1: Remote dispatch
2: Local control
0
0
2
0
0
2
0
0
2
Percentage
Local electric
dispatch Active
Power setting value
0
100
100
0
100
100
0
100
100
Table 6-14 Power Derating Setup
Only for CPS SCA25KTL-DO-US-208
Grid Over Frequency
Derating
Setting Range
Parameter Name
LCD Display
Description
IEEE1547
Rule21
Min
Default Max
Min
Default
Max
VwcurveV1(%)
Grid overvoltage
derating starting
voltage V1
105.00
106.00
109.00 105.00
106.00
109.00
VwcurveP1(%)
Grid overvoltage
derating starting
power P1
0.0
100.0
100.0 0.0
100.0
100.0
VwcurveV2(%)
Grid overvoltage
derating end voltage
V2
106.00
110.00
110.00 106.00
110.00
110.00
VwcurveP2(%)
Grid overvoltage
derating end power
P2
0.0
0.0
100.0
0.0
0.0
100.0