(3) RS485 network connection:
When the inverters are monitored via the RS485 communication, the unique
RS485 address for each inverter can be set through the LCD interface. Up to 31
inverters can be connected together in the RS485 communication network. The
Daisy-chain topology is recommended for the RS485 network connection, as shown
in Figure 3-20. Other communication topologies, such as the star networks, are not
recommended.
1
Datalogger
2
N
Figure 3-20 RS485 connection between inverters and datalogger
(4) A terminal resistance of 120 ohms connected between Pin 1 and Pin 3 of
RS485-1/2 of the last inverter in the multiple inverters string and data logger as
shown in Figure 3-20 is recommended.
(5) The connection inside the Wiring box of the inverter after the first one
is shown in Figure 3-21: