41
2. Grounding is abnormal;
3. Fault inside the inverter
Recommended solutions:
1. Observe for 10 minutes and see whether the
alarm will be eliminated automatically;
2.. Detect whether the electrical connection is
abnormal
3. Contact after-sales service personnel
7. IsolationErr
Definition:
Insulation impedance of PV positive to ground
or PV negative to ground exceeds the specified
range
Possible causes:
Air humidity is high
Recommended solutions:
1. Observe for 10 minutes and see whether the
alarm will be eliminated automatically;
2. Check insulation of PV system;
3. Contact after-sales service personnel
8.
IntProtect0010-01
80
Definition:
Internal protection of the inverter
Possible causes:
Protection procedure occurs inside the inverter
Recommended solutions:
1. Observe for 10 minutes and see whether the
alarm will be eliminated automatically;
2. Contact after-sales service personnel
Fault
IntFault0010-0150 Definition: