 Operating Manual 

 

 

4-1

4 Configuration and Programming 

4.1 

Selecting connected device options (DIP switches) 

A series of DIP switches are used to configure devices connected to the fire alarm control panel. DIP 
switches are located in the lower right corner of the panel. 

 

 

DIP Switch  9 

Description of Disabled States 

(Switch to left side) 

Description of Enabled States 

(Switch to right side) 

1.  B1 Strobe 

NAC 1 devices are silenceable. 

NAC 1 devices are non-silenceable – 
requires panel reset to silence. 

2.  B1 Temporal 

NAC 1 rings constant 

NAC 1 rings for 3 pulses and then stops 
for 1 pulse (1/2 second per pulse) 

3.  TRBL-REM ALM  Remote alarm trouble disabled. 

Remote alarm trouble enabled. 

4.  ANNUNC DISC 

Remote annunciator is not used or 
annunciator input is ignored. 

Remote annunciator is used and 
annunciator input is accepted. 

5.  Z1- Waterflow 

Zone not waterflow switch (silenceable) 

Zone waterflow switch (not silenceable) 

6.  Z1- Verify 

Zone not verify 

Zone verify 

7.  Z1- Class A 

Zone Style B (Class B) 

Zone Style D (Class A) 

8.  Z2- Waterflow 

Zone not waterflow switch (silenceable) 

Zone waterflow  switch (not silenceable) 

9.  Z2-Verify 

Zone not verify 

Zone Verify 

10. Z2- Class A 

Zone Style B (Class B) 

Zone Style D (Class A) 

 

DIP Switch 10 

Description of Disabled States 
(Switch to left side) 

Description of Enabled States 
(Switch to right side) 

1. Z3- Waterflow 

Zone not waterflow switch (silenceable) 

Zone waterflow switch (not silenceable) 

2. Z3- Verify 

Zone not verify 

Zone verify 

3. Z3- Class A 

Zone Style B (Class B) 

Zone Style D (Class A) 

4. Z4- Waterflow 

Zone not waterflow switch (silenceable) 

Zone waterflow switch (not silenceable) 

5. Z4- Verify 

Zone not verify 

Zone verify 

6. Z4-Class A 

Zone Style B (Class B) 

Zone Style D (Class A) 

4.1.1 

B1 Strobe device 

Place the 

B1 STROBE 

switch in the “on” position (right side of the switch) when NAC 1 is a non-

silenceable circuit (for devices such as strobes). When enabled, the circuit cannot be silenced during 
alarm except by resetting the panel. 

4.1.2 

B1 Temporal pattern 

Place the 

B1 TEMPORAL

 switch in the “on” position (right side of the switch) when you wish NAC 1 to 

ring a temporal pattern. A temporal signal consists of three rings and one pause as defined by NFPA 72, 
Section A-3-7.2 (2). 

Figure 4-1. DIP Switches 

Содержание FIRELARM 2500

Страница 1: ...G Signals 2519 4th Ave P O Box 590 Moline IL 61265 800 577 5758 309 762 0731 FAX 309 762 8215 www cpglifesafety com CPG 2561255 Rev A 0209 OPERATING MANUAL FIRELARM 2500 4 ZONE FIRE ALARM CONTROL PANE...

Страница 2: ...CPG 2561255 FIRELARM 2500 Operating Manual Warranty CPG products are covered by a limited warranty See CPG s warranty statement for more information document 780 0762...

Страница 3: ...2 5 6 2 4 2 5 7 Initiating circuit alarm 2 4 2 5 8 Auxiliary power output conditions 2 5 2 5 9 Battery power conditions 2 5 2 5 10 AC power conditions 2 5 2 5 11 System trouble 2 5 2 5 12 Supervisory...

Страница 4: ...feature One man test 5 1 5 2 Inspection and Test procedure 5 1 5 2 1 Testing the control panel 5 1 5 2 2 Testing the Remote Annunciator 5 2 5 2 3 Testing the Zonal Digital Alarm Communicator Transmitt...

Страница 5: ...s B Optional Style Z Class A module available 2 5 Amps total current for NAC and auxiliary power circuits 1 supervisory initiating zone Reverse polarity output for alarm or alarm and trouble signals R...

Страница 6: ...2 5A power limited 2 7mA 5 1K ohms Initiating Device Circuits Zones Smoke capacity 24VDC Standby voltage Max ripple voltage Max short circuit current Normal standby current Alarm current threshold Ma...

Страница 7: ...Red Knockouts Combination 2 on each side top and back Option Bezel trim for semi flush mounting 1 3 3 Service use NFPA 72 Local Auxiliary PPU Remote Station PPU Central Station PPU PPU Protected Prem...

Страница 8: ...Contents 1 CPG 2561255 FIRELARM 2500 Operating Manual 1 4...

Страница 9: ...vent a subsequent alarm or trouble from another zone Toggles one man test mode See section 5 1 Auto Reset Toggles reverse polarity circuits from generating alarm or trouble condition causes system tro...

Страница 10: ...y of 1 Numeric entry of 2 Numeric entry of 3 Numeric entry of 4 Numeric entry of 5 Numeric entry of 6 Numeric entry of 7 Numeric entry of 8 Numeric entry of 9 Numeric entry of 0 YES Confirm change of...

Страница 11: ...4 3 Resetting a trouble condition Determine the cause of the trouble condition and remove the cause This condition is self restoring When all trouble conditions are removed all indications will return...

Страница 12: ...eration of all system trouble indications see section 2 5 11 System trouble SUPERVISORY TROUBLE CONDITION is displayed on the optional LCD 2 5 5 Initiating zone trouble An increase in current to a lev...

Страница 13: ...age would result in the following Green AC LED will be extinguished Operation of all system trouble indications see section 2 5 11 System trouble AC TROUBLE will be displayed on the optional LCD 2 5 1...

Страница 14: ...1 Contents 2 CPG 2561255 FIRELARM 2500 Operating Manual 2 6...

Страница 15: ...After installation and completion of final test provide a copy of this instruction manual to all personnel responsible for operation periodic testing and maintenance of this system 3 2 NFPA and UL in...

Страница 16: ...om the floor where it will be accessible for testing and servicing 3 The main circuit board module can be removed before attempting to mount the cabinet Disconnect the two wires of the transformer fro...

Страница 17: ...cks Peel off the small adhesive label at the edge of the large black plastic LED label so that the ZDACT LED s can be viewed from the front Reconnect AC power and battery power 3 7 Battery size requir...

Страница 18: ...larm Code Standby Time Alarm Time Local Systems Auxiliary Systems Remote Station Systems Central Station Systems 24 hrs 60 hrs 60 hrs 24 hrs 5 min 5 min 5 min 5 min Table 3 3 Calculation Table 1 2 3 4...

Страница 19: ...ire detector connections Style B Class B cuircuit 290 0006 4 WIRE DETECTORS N O N O N O ZONE TERMINALS ALL CONTACTS SHOWN IN NORMAL STANDBY CONDITION 290 0007 42 43 OUT IN OUT IN OUT IN EOL RESISTOR 5...

Страница 20: ...ATOR SUPERVISED 2 MAX 100mA PER UNIT TYPICAL STYLE D CLASS A WIRING USE N O SUPV SWITCHES INTENDED FOR CONNECTION TO A POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVEING UNIT THAT HAS COMPATIBLE...

Страница 21: ...tem current not to exceed 2 5 A Notes for Figure 3 7 1 Power inputs not power limited Wire wrap to standoff for strain relief 2 Battery leads not power limited 3 Use left hand knockouts for non power...

Страница 22: ...Contents 1 2 3 CPG 2561255 FIRELARM 2500 Operating Manual 3 8...

Страница 23: ...B Zone Style D Class A 8 Z2 Waterflow Zone not waterflow switch silenceable Zone waterflow switch not silenceable 9 Z2 Verify Zone not verify Zone Verify 10 Z2 Class A Zone Style B Class B Zone Style...

Страница 24: ...on device 4 1 6 Alarm verification Place the VERIFY switch in the on position right side of the switch to place a zone in the alarm verification mode This mode should only be used with smoke detectors...

Страница 25: ...xit configuration To skip zone setup and go to password setup To skip zone setup and go to ZDACT setup if used ENTER ZONE 1 DESCRIPTION To program the label for zone 1 To exit to SET UP ZONES Screen o...

Страница 26: ...ZDACT configuration and go to AC trouble reporting delay configuration ENTER PHONE NUMBER 1 To enter phone number 1 To exit to SETUP ZDACT screen or To cycle forward or backward through ZDACT configu...

Страница 27: ...trouble reporting configuration and go to ZDACT configuration if used To skip AC trouble reporting configuration and go to password configuration AC DELAY HR or To change the value To save the value...

Страница 28: ...word 2402 Change the password write it down and store in a safe place for optimum protection CHANGE PASSWORD To change the password To exit configuration mode To skip password configuration and go to...

Страница 29: ...hibited by pressing In addition to the testing procedures described below the FireLarm 2500 system and all of its associated protective signaling adjuncts should be inspected and tested in accordance...

Страница 30: ...ors connected to the notification appliance circuit should be off 12 The supervising station will also be restored to normal if applicable 5 2 2 Testing the Remote Annunciator 1 Verify that the contro...

Страница 31: ...nnunciator 2 Keypad operates the same as on the panel except as noted below Key Function Control When Active ACK Silences buzzer on RALCD only Annunciator Always TEST Turns on buzzer backlight if off...

Страница 32: ...in trouble a report is sent to the supervising station and the Line Fault trouble LED D3 is illuminated for local indication The Panel Supervisory trouble LED D2 will illuminate if communication with...

Страница 33: ...A circuit one module is required for each notification appliance circuit The module is provided with snap track which is mounted to the cabinet via double sided foam tape and secured by two 6 sheet me...

Страница 34: ...ox is supervised to detect an open circuit Terminals are provided for the connection of the master box reset supervisory contacts A switch is provided to disable the unit so that it will not trip the...

Страница 35: ...ppled to the fire alarm control panel CAUTION This module must be installed in accordance with all applicable sections of NFPA 72 the National Electrical Code all local codes and any authority having...

Страница 36: ...1 2 3 4 5 Contents A CPG 2561255 FIRELARM 2500 Operating Manual A 6...

Страница 37: ...1U S11A 702 702E 701RU or 701RE 731UD S11A 702U or 702E 732U S11A 702 702E 701RU or 701RE S00 for all SYSTEM SENSOR BRK MAX NO OF DETECTORS PER ZONE IS 20 DET MODEL IDENTIFIER BASE MODEL IDENTIFIER 14...

Страница 38: ...1 2 3 4 5 A Contents B CPG 2561255 FIRELARM 2500 Operating Manual B 2...

Страница 39: ...oor horn strobes MHSG0 series mini horn strobes SSG1 SSG0 SSTG0 SSF0 SSWPF0 series strobes 2G1AVCMS 4G0CMS strobe synchronizers SMF0 series strobe synchronizers 4 LPSPKF0 8 LPSPKF0 series speakers ACV...

Страница 40: ...Contents C CPG 2561255 FIRELARM 2500 Operating Manual C 2 4415 4495 series AC chimes 4765 4775 series DC chimes 3431 3436 4496 4411 4416 series AC bells 4461 4464 4466 4761 4764 4766 4771 4774 4776 se...

Страница 41: ...AH 2 required for 24V 313 0265 Options Model No Description Stock No BT Bezel Trim for Semi Flush Mounting black 2500 BT PAM 1 Relay for 4 wire detector supervision PAM 1 PAM 2 Relay for 4 wire detect...

Страница 42: ...C B 1 2 3 4 5 A Contents D CPG 2561255 FIRELARM 2500 Operating Manual D 2...

Страница 43: ...ve closed low air low temperature etc To Silence Trouble Devices Open cover and press The panel automatically restores to normal when the trouble condition has been corrected Some trouble conditions r...

Страница 44: ...D C B 1 2 3 4 5 A Contents E CPG 2561255 FIRELARM 2500 Operating Manual E 2...

Отзывы: