1
2
3
4
Content
s
5
CPG #2561255
F
IRE
L
ARM
2500
Operating Manual
5-2
7.
Press
. All audible and visual indicators on the panel and NAC outputs should operate.
Restore AC power and verify panel is in normal standby condition.
8. Press
to enter auto reset mode.
9. Operate each initiating device on all zones. All audible and visual notification appliances should
operate. NAC devices pulse the zone number. Power is then removed from the initiating device circuit
for approximately 7 seconds. No alarms can be initiated during this test. If the initiating device has not
been restored the panel will repeat the test pulse.
10. Operate each initiating device on the supervisory circuit. Observe that all the indications occur as
described in section 2.5.12
Supervisory initiating device circuit
.
11. Press
to exit auto-reset mode. If
had been pressed to enable it, press it to disable it.
All the LEDs on the panel except the green AC ON LED should be off. All audible and visual
indicators connected to the notification appliance circuit should be off.
12. The supervising station will also be restored to normal (if applicable).
5.2.2
Testing the Remote Annunciator
1. Verify that the control panel is in normal standby condition.
2. Press and hold TEST on the remote annunciator. Verify that all visual and audible indicators on the
annunciator are operating. Release TEST.
3. Turn the annunciator keyswitch to the on position. Press RESET. Verify that the annunciator displays
the reset countdown
5.2.3
Testing the Zonal Digital Alarm Communicator Transmitter (ZDACT)
1. Initiate a signal while the ZDACT is connected to the primary telephone line.
2. Disconnect the primary line from the ZDACT. Verify that the ZDACT trouble signal is indicated on the
control panel and that the trouble signal is transmitted to the supervising station.
3. Disconnect the secondary line from the ZDACT. Verify that the ZDACT trouble signal is indicated on
the control panel and that the trouble signal is transmitted to the supervising station.
4. Simulate a fault in the primary telephone number. Verify that the ZDACT uses the secondary
telephone number to complete the transmission..
Содержание FIRELARM 2500
Страница 8: ...Contents 1 CPG 2561255 FIRELARM 2500 Operating Manual 1 4...
Страница 14: ...1 Contents 2 CPG 2561255 FIRELARM 2500 Operating Manual 2 6...
Страница 22: ...Contents 1 2 3 CPG 2561255 FIRELARM 2500 Operating Manual 3 8...
Страница 36: ...1 2 3 4 5 Contents A CPG 2561255 FIRELARM 2500 Operating Manual A 6...
Страница 38: ...1 2 3 4 5 A Contents B CPG 2561255 FIRELARM 2500 Operating Manual B 2...
Страница 42: ...C B 1 2 3 4 5 A Contents D CPG 2561255 FIRELARM 2500 Operating Manual D 2...
Страница 44: ...D C B 1 2 3 4 5 A Contents E CPG 2561255 FIRELARM 2500 Operating Manual E 2...