Operating Manual
3-7
3.8
Notification Appliance Circuits Connections
The control panel has two Style Y (Class B) notification appliance circuits which can be upgraded to Style
Z (class A) by the addition of a model CAM (Class A Module). One module is required for each circuit that
is to be upgraded. See Appendix A for more information.
The notification appliance circuits are power limited, regulated 24 VDC rated at 2.0 amperes max each.
(Total system current not to exceed 2.5 A.)
Notes for Figure 3-7:
1.
Power inputs (not power limited). Wire wrap to standoff for strain relief.
2.
Battery leads (not power limited).
3.
Use left hand knockouts for non-power limited wiring.
4.
Use right hand knockouts for power limited wiring.
5.
Connect earth ground to corner of main board using a #6 ring terminal or wire and
ring provided.
6.
All wiring must be wire-wrapped to a standoff or other mechanically secure location.
All field-installed wiring connected to this panel must maintain a spacing of ¼
inch between all power-limited conductors and all electrical light, power,
Class 1, or non-power limited conductors.
Figure 3-7. Wire Routing
Diagram
290-0009
Содержание FIRELARM 2500
Страница 8: ...Contents 1 CPG 2561255 FIRELARM 2500 Operating Manual 1 4...
Страница 14: ...1 Contents 2 CPG 2561255 FIRELARM 2500 Operating Manual 2 6...
Страница 22: ...Contents 1 2 3 CPG 2561255 FIRELARM 2500 Operating Manual 3 8...
Страница 36: ...1 2 3 4 5 Contents A CPG 2561255 FIRELARM 2500 Operating Manual A 6...
Страница 38: ...1 2 3 4 5 A Contents B CPG 2561255 FIRELARM 2500 Operating Manual B 2...
Страница 42: ...C B 1 2 3 4 5 A Contents D CPG 2561255 FIRELARM 2500 Operating Manual D 2...
Страница 44: ...D C B 1 2 3 4 5 A Contents E CPG 2561255 FIRELARM 2500 Operating Manual E 2...