Appendix A. Optional Accessories
A.1
Remote Annunciator with Liquid Crystal Display (2500-RALCD)
Part # 2500-RALCD
UL Listed: For use with the
FireLarm 2500
Dimensions: 4 ½” W X 4 ½” H X 7/8” D (approximate)
Weight: 5.5 OZ.
Enclosure: Stainless steel plate. Mounts on standard double-gang switch box or 4” square box
using adapter plate.
Power Requirements: 24VDC @ 115mA max. – Obtained from control panel.
Line resistance: 25 ohms max
The Model RALCD is a Remote Annunciator that is designed to operate with the
FireLarm 2500
Fire
Control Panel. This unit will mount on a standard 2-gang switch box. The LCD displays the same
information as on the main panel. A built in buzzer sounds when a trouble condition exists on the panel.
Two annunciators can be connected in parallel. Jumper SW7 must be shorted to specify annunciator 1,
and must be open to specify annunciator 2.
Keypad – operates the same as on the panel except as noted below.
Key Function Control
When
Active
ACK
Silences buzzer on RALCD only.
Annunciator
Always
TEST
Turns on buzzer, backlight (if off), and scrolls through
alphabet.
Annunciator Always
RESET
Resets all alarm circuits if condition has been corrected,
removes power from initiating device circuit and auxiliary
power from smoke detectors for 7 seconds.
Panel
Key switch on
DRILL
Pressing for 2 seconds will initiate a fire drill.
Panel
Key switch on
SCROLL Scrolls through trouble conditions, if present.
Panel
Key switch on
SILENCE Press once to silence buzzers on panel and annunciators.
Press again to silence signal circuits.
Panel
Key switch on
Electrical Connections
RALCD Terminal
Function of Terminal
FireLarm 2500
Terminal (TB4)
D Data
signal
D
D*
Data inverted signal
D*
GND Power
ground
GND
+24 VDC
Power
+24 VDC
EARTH
Earth ground (optional connection) E
Fire Alarm Annunciator
LIQUID CRYSTAL
DISPLAY
KEY SWITCH
KEY SWITCH
CONTROL
OFF
TEST
SCROLL
SILENCE
DRILL
HOLD 2 SECS
ACK
RESET
290-0011
Figure A-1. LCD Remote Annunciator
Содержание FIRELARM 2500
Страница 8: ...Contents 1 CPG 2561255 FIRELARM 2500 Operating Manual 1 4...
Страница 14: ...1 Contents 2 CPG 2561255 FIRELARM 2500 Operating Manual 2 6...
Страница 22: ...Contents 1 2 3 CPG 2561255 FIRELARM 2500 Operating Manual 3 8...
Страница 36: ...1 2 3 4 5 Contents A CPG 2561255 FIRELARM 2500 Operating Manual A 6...
Страница 38: ...1 2 3 4 5 A Contents B CPG 2561255 FIRELARM 2500 Operating Manual B 2...
Страница 42: ...C B 1 2 3 4 5 A Contents D CPG 2561255 FIRELARM 2500 Operating Manual D 2...
Страница 44: ...D C B 1 2 3 4 5 A Contents E CPG 2561255 FIRELARM 2500 Operating Manual E 2...