Installation
Mounting
DA
DA
DALI
Choosing a Suitable Location
The detector should be sited so that the occupants of the room fall inside the detection pattern shown on page 1, at a
recommended ceiling height of 2.8m. Note that the lower the sensor is installed the smaller the detection range will be,
subject to the parameters shown on the detection diagram.
Avoid direct sunlight entering the sensor.
Do not site within 1m of forced air heating or ventilation.
Do not fix to a vibrating surface.
Do not exceed maximum length of cable (200m) on data bus.
Do not exceed maximum bus loading (200mA).
Wiring diagram
The EBR-MINPIR-DALI supplied with two 1m wires to
connect to the DALI network. The device is designed to
operate correctly with reversed polarity.
Remove bottom
of 2 small
retention arms
Standalone mounting
The product is designed to be mounted into a ceiling tile or plasterboard ceiling using the flush holder as shown below. If
flush mounting in a panel >6mm thick, remove bottom of retention arms with side cutters.
Luminaire mounting
The product is also designed to be mounted directly to a luminaire, either on the inside or outside.
The PIR lens must have a view outside the luminaire.
For optimum lux measurement, the lens must be shielded as much as possible from the light source.
If flush mounting in a panel >6mm thick, remove bottom of retention arms with side cutters.
Flush mounting
The product can be mounted using the
flush mount ring as shown. If flush
mounting in a material that is greater
than 6mm thick, remove bottom of
retention arms with side cutters. A
32mm diameter hole will be required to
mount the flush mount ring.
Ø19.5m
Ø3.5m
19mm
Use the lugs on rear of detector to
secure into thin sheet metal (1mm
max.).
Surface mounting
Devices (detectors / input units) and ballast combinations
for 200mA supply.
This
assumes that the sensor LEDs are all on, and the
sensor is receiving IR communication.
4
devices
and up to 64 ballasts
5 devices and up to 55 ballasts
6 devices and up to 44 ballasts
7 devices and up to 33 ballasts
8 devices and up to 22 ballasts
9 devices and up to 12 ballasts
10 devices and up to 2 ballasts
In most realistic scenarios, only one LED is on at a time
and only one detector is receiving IR; guidance changes
to.
10 devices up to 64 ballasts
11 devices up to 60 ballasts
12 devices up to 55 ballasts
13 devices up to 50 ballasts
14 devices up to 48 ballasts
15 devices up to 44 ballasts
Addressing limits of DG64
5 input units of 7 channels each
10 detectors
DALI bus loading