COSTAN TECHNICAL DOCUMENTATION
REVISION STATUS
TRUE COPY
PAGE 20 OF 22
PRODUCT:
EPTAGLOO
ORD
DATE
CHANGE ORDER
OF THE SIGNED
DATE OF 1st ISSUE
A
18.Dec.2008
UPDATING
ORIGINAL
13/June/07
DOC. no. QSM0000406A
CHAP. No.:
020
B
28.July.2009
UPDATE OF. SF ENTERING
OF. NC
CHAPTER:
DESCRIPTION / TECHNICAL
C
23.Feb.2010
RANGE
EXTENSION
DETAILS
D
11.Nov..2010
SAFETY VALVE ADDED
ISSUED BY MKT
Low-temperature applications – 3 Frascold compressors
TAB.5B
Pack model
3 X Q 4 19.1 Y
3
X
Q 4 21.1 Y
3 X Q 5 28.1 Y
Power voltage
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Number of compressors
3
3
3
Refrigerant
R404A R404A R404A
Heat extraction rate
1
(W)
7023
8856
13305
Power input
1
(W) 5907
7041
10227
Maximum power
2
(W)
14622 16542 23580
Maximum power input
3
(A)
27,3
30
42
Pipework
Cond. discharge diameter (mm)
16
22
22
Diameter of condenser return line (mm)
22
22
22
Diameter of suction line (mm)
42
54
54
Dimensions and weights
4
Length
(mm)
2070 2070 2070
Width (mm)
990
990
990
Height
(mm)
1380 1380 1380
Weight (kg)
753
768
768
Compressor
Q 4 19.1 Y
Q 4 21.1 Y
Q 5 28.1 Y
Type
semi-hermetic reciprocating
semi-hermetic reciprocating
semi-hermetic reciprocating
Brand
Frascold Frascold Frascold
Series
Series Q
Series Q
Series Q
Frascold lubricant
Oil Frascold POE 32
Oil Frascold POE 32
Oil Frascold POE 32
Power input under operation
1
(A)
5,19 5,54 6,87
Max. power input
3
(A)
9,1
10
14
Liquid receiver vessel
Volume of liquid receiver vessel (L)
40
40
40
Diameter of liquid line (in/out) (mm)
22
22
22
Electrical panel (400/3/50)
Code of el.panel with OCD (overcurrent
protection)
UQ391AM8E UQ391AM9E UQ391AMAE
Code of el.panel with RCBO UQ391AD8E
UQ391AD9E
UQ391ADAE
Range of overcurrent device to protect
compressors
(7 – 10)A
(9 – 12,5)A
(11 – 16)A
Carel Controller
IR32Z3 IR32Z3 IR32Z3
Danfoss Controller
EKC331/T EKC331/T EKC331/T
Carel Controller
PCO3 PCO3 PCO3
Danfoss Controller
AK-PC530 AK-PC530 AK-PC530
Carel Controller
mRACK
mRACK
mRACK
1
Data calculated using software Frascold version 1.2.0.0 at conditions Te=-35ºC ; Tc=+40ºC ; Suction gas temp. =20ºC ; liquid subcooling 0K
(pursuant to Directive EN12900). The value for the power input does not include condenser fans nor the one that is optionally fitted on the hood; it
only refers to compressors and does not consider power-factor improving capacitors.
2
Data calculated using software Frascold version 1.2.0.0 at limit use conditions for the specified compressor.
3
Technical data for Frascold compressors as in document FCAT01-15.
4
The data in the table refer to the version with enclosure and complete oil circuit.
Содержание EPTAGLOO
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......