Medium-temperature applications – 4 Frascold compressors
TAB.8B
Pack model
4 X S 7 39 Y
4 X S 10 51 Y
4 X S 15 56 Y
Power voltage
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Number of compressors
4
4
4
Refrigerant
R404A R404A R404A
Heat extraction rate
1
(W)
85668
111580
126404
Power input
1
(W) 35336
46840
49712
Maximum power
2
(W)
40039
50320
63028
Maximum power input
3
(A)
76,8
96,8
122,8
Pipework
Cond. discharge diameter (mm)
42
54
54
Diameter of condenser return line (mm)
42
42
42
Diameter of suction line (mm)
80
80
80
Dimensions and weights
4
Length
(mm)
2570 2570 2570
Width (mm)
990
990
990
Height
(mm)
1380 1380 1380
Weight
(kg)
1177 1190 1230
Compressor
S 7 39 Y
S 10 51 Y
S 15 56 Y
Type
semi-hermetic reciprocating
semi-hermetic reciprocating
semi-hermetic reciprocating
Brand
Frascold Frascold Frascold
Series
Series S
Series S
Series S
Frascold Lube
Oil Frascold POE 32
Oil Frascold POE 32
Oil Frascold POE 32
Power input under operation
1
(A)
15,63 20,54 24,13
Max. power input
3
(A)
19,2 24,2 30,7
Liquid receiver vessel
Volume of liquid receiver vessel (L)
60
60
60
Diameter of liquid line (in/out) (mm)
28
28
28
Electrical panel (400/3/50)
Code of el.panel with OCD (overcurrent
protection)
UQ391DMBE UQ391DMCE UQ391DMDE
Code of el.panel with RCBO UQ391DDBE
UQ391DDCE
UQ391DDDE
Range of overcurrent device to protect
compressors
(14 – 20)A
(20 - 25)A
(22 – 32)A
Carel Controller
IR32Z3 IR32Z3 IR32Z3
Danfoss Controller
EKC331/T EKC331/T EKC331/T
Carel Controller
PCO3 PCO3 PCO3
Danfoss Controller
AK-PC530 AK-PC530 AK-PC530
Carel Controller
mRACK
mRACK
mRACK
1
Data calculated using software Frascold version 1.2.0.0 at conditions Te=-10ºC ; Tc=+40ºC ; Suction gas temp. =20ºC ; liquid subcooling 0K
(pursuant to Directive EN12900). The value for the power input does not include condenser fans nor the one that is optionally fitted on the hood; it
only refers to compressors and does not consider power-factor improving capacitors.
2
Data calculated using software Frascold version 1.2.0.0 at limit use conditions for the specified compressor.
3
Technical data for Frascold compressors as in document FCAT01-15.
4
The data in the table refer to the version with enclosure and complete oil circuit.
Содержание EPTAGLOO
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......