8.13 - Checking the ionisation current
In any operating status, also during verifications of minimum
and maximum power stated in section 8.12, the ionisation
current value can be consulted on parameter
1008
present
in the “User menu” (section 7.7). This value must be between
1,5 and 3 uA (microampere) at minimum power and between
5 and 8 uA at maximum power.
8.14 - Water temperature measurement
sensor testing procedures
The temperature sensors are positioned on the appliances’
exchanger body. The electric resistance existing between
the two contacts of the sensor, must correspond with that
stated in figure 8-11.
The temperature sensors are:
1001
,
1002
,
1003
,
1005
,
1006
,
1007
and
1014
, the positioning of
which can be verified in figures 3-1, 3-2, 3-3 and 3-4.