4 Series/Parallel Operation

4.1 Series Operation

¡

Wiring method with series operation is shown in Fig.4.1.

  The MS and SGND must be connected with each other.
  Please use option part H-PA-14 for connecting between MS and 

SGND.

  Please decide one power supply (master power supply) to be op-

erated on the volume and short circuit between SLV_EN and COM 
of the other power supply (slave power supply).

  To short-circuit between SLV_EN and COM, please use option 

part H-SN-53.

  Use the Master when changing the output voltage.
  If one of the units operated in series stops or fails, all the power 

supplies are stopped by signal information of the MS terminal.

  To start / stop use the remote ON/OFF control function. Connect 

RC 2 and RCG of all power supplies to be operated in series and 
start / stop all at the same time.

  It is necessary to turn the power supply on again to switch the 

mode of Master/slave.

  When using in series operation, use products of the same model 

name.

Implement H-PA-14

Implement H-SN-53

Load

No.3 (Slave)

No.2 (Slave)

No.1 (Master)

Fig.4.1  Connection method in series

*

 Notes on series operation

(1)  Constant current set value external variable function cannot be 

used.

(2)  When the overcurrent condition occurs, the latch stop operation 

is performed.

     In order to release the latch stop operation, input is shut down 

and input is restarted after 10 seconds or setting the voltage of 
RC2 terminal to logic to turn off output.

4.2 Parallel Operation/Master-slave Operation

¡

Wiring method with series operation is shown in Fig.4.2.

  The MS and SGND must be connected with each other.
  Please use option part H-PA-14 for connecting between MS and 

SGND.

  Please decide one power supply (master power supply) to be op-

erated on the volume and short circuit between SLV_EN and COM 
of the other power supply (slave power supply).

  To short-circuit between SLV_EN and COM, please use option 

part H-SN-53.

  Use the Master to change the output voltage.
  If one of the units operating in parallel stops or fails, all the power 

supplies are stopped by signal information of the MS terminal.

  To start / stop use the remote ON/OFF control function. Connect 

RC 2 and RCG of all power supplies to be operated in parallel and 
start / stop all at the same time.

  It is necessary to turn the power supply on again to switch the 

mode of the Master/slave.

  When using in parallel operation, use products of the same model 

name.

  As variance of output current drew from each power supply is 

maximum 10%, the total output current must not exceed the value 
determined by the following equation.

  (Output current at parallel operation) 
  = (the rated current per unit) × (number of unit) × 0.9

¡

When the number of units in parallel operation increases, the in-
put current also increases.  Please design input circuitry (including 
circuit pattern, wiring and current capacity for equipment) carefully.

¡

Please make sure that the wiring impedance of a load from each 
power supply becomes even.  Otherwise, the output current bal-
ance circuit may become inoperative.

¡

The maximum number of units you can use in parallel operation is 
3.

AC-DC Power Supplies Enclosed Type

Instruction Manual

PCA-13

Содержание PCA600F

Страница 1: ...Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series operation Parallel operation PCA600F Active filter 15 400 7 3 250V 16A R...

Страница 2: ...5 Assembling and Installation Method PCA 14 4 1 Series Operation PCA 13 4 2 Parallel Operation Master slave Operation PCA 13 5 1 Installation Method PCA 14 5 2 Derating PCA 15 5 3 Life expectancy and...

Страница 3: ...G Each terminal of CN1 and CN2 are connected inside the power supply Table 1 2 Pin Configuration and Functions of CN3 Pin No Function Ground level 1 AUX Auxiliary output AUXG 2 AUXG Auxiliary output g...

Страница 4: ...ient temperature 50 to 70 should be not more than the calculated value by linear interpolation Point A Fig 2 1 Temperature measurement point A thin electric wire could heat up and affect the power sup...

Страница 5: ...al to logic to turn off output Note Please avoid applying a voltage exceeding the rated voltage to an output terminal Doing so may cause power supply to malfunction or fail If this is unavoidable for...

Страница 6: ...pecifications of remote ON OFF Connection method Fig 3 1 a Fig 3 1 b Fig 3 1 c SW Logic Output ON SW open 0 1mA max SW open 0 1mA max SW close 0 5V max Output OFF SW close 3mA min SW close 3mA min SW...

Страница 7: ...the power supply stops Open collector method Good Low 0 5V max at 5mA Bad High 50V 5mA max 100kW 0 1mF PG PGG Fig 3 4 Internal circuit of PG Please note the followings when you use the alarms PG sign...

Страница 8: ...peration Wiring method with series operation is shown in Fig 4 2 The MS and SGND must be connected with each other Please use option part H PA 14 for connecting between MS and SGND Please decide one p...

Страница 9: ...er 10 seconds or setting the voltage of RC2 terminal to logic to turn off output 5 Assembling and Installation Method 5 1 Installation Method To keep enough isolation between screws and internal compo...

Страница 10: ...ectancy Mount Average ambient temperature yearly Life expectancy 0 Io 50 50 Io 100 All mounting direction Ta 35C 8 years 6 years Ta 40C 7 years 5 years Ta 50C 6 years 4 years Life expectancy R t 90 of...

Страница 11: ...e a voltage a few times higher than the applied voltage When you test a unit for isolation between the input and output input and the terminal FG or between the output and the terminal FG short circui...

Страница 12: ...0VAC When ambient temperature is 40 or less point B is 70 or less When ambient temperature is 70 point B is 75 or less The ambient temperature 40 to 70 should be not more than the calculated value by...

Отзывы: