UC 700 Series Continus-Flow Icemaker Installation/Service Manual
© 2000-2011, IMI Cornelius Inc.
- 13 -
Publication Number: 630460127
REFRIGERATION SYSTEM
NOTE:Thermostatic Expansion Valve No Adjustment
+/-10 lbs. Discharge Pressure
WATER TEMPERATURE
R
EFRIGERATION
S
YSTEM
A
DJUSTMENTS
A complete understanding of the icemaker and hermetic refrigeration system is necessary before any adjustments
are made. The refrigeration technician must use high and low side pressure readings, water and air temperatures,
plus general conditions of cleanliness to assess the refrigeration system status when making any adjustments.
All icemaker products are tested and adjusted at the factory prior to shipment where the ambient temperature
ranges from 65° to 90°F, depending on the season of the year.
Whenever a new icemaker product is initially installed and started–up, it is imperative that the start–up operation
make the following checks and/or readjustments for local conditions.
E
XPANSION
V
ALVE
You will find a thermostatic expansion valve on icemakers, which is used to control the amount of refrigerant flowing
through the evaporator. Improperly installed or defective expansion valves may cause low production, soft ice,
squeaking from evaporator and excessive load inside evaporator.
By using general refrigeration system troubleshooting along with the pressure charts you can easily determine
whether or not the expansion valve is working properly.
WCC 700
40°
65°
90°
50°
174
177
180
60°
202
205
208
70°
230
233
236
80°
265
269
272
90°
300
304
307
100°
328
334
340
Ai
r T
e
m
p
e
rat
ur
e