Section 363-718-102
May 30, 1997
Revision 01
Page 28
PairGain Engineering - Plant Series
PG-Flex FCS-718
8.9
Fuse.
Insert a 3 amp fuse in the equipment bay fuse panel for each circuit (two) where the PG-Flex
CO battery wire is terminated.
8.10
Cabling Verification.
Verify the following:
The following verifications should be done before any cards are inserted in the
COT shelf.
1
Verify a minimum of -42 Vdc and a maximum of -56 Vdc between:
a
TB1 BATT A (–48 Vdc) and TB3 (BATT RTN) screw terminals on the COT shelf.
b
TB2 BATT B (–48 Vdc) and TB3 (BATT RTN) screw terminals on the COT shelf.
2
Verify the following for the HDSL lines:
If the HDSL lines are not connected properly, the COT will not communicate
with the RT.
a
Visually verify the HDSL lines are terminated properly and with the correct polarity.
b
Verify that the HDSL lines are "dry."
c
Verify 0 Vdc between the Tip and Ring, Tip and Ground, and Ring and Ground of each of
the HDSL circuits terminated on the shelf.
d
Verify > 100 kohm resistance between the Tip and Ring, Tip and Ground, and Ring and
Ground of each of the HDSL circuits terminated on the shelf.
3
Replace the clear Plexiglas cover on the rear of the COT shelf.