![CopperOptics 150-1318-02 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/copperoptics/150-1318-02/150-1318-02_manual_2666214025.webp)
Revision 01
May 30, 1997
Section 363-718-102
PG-Flex FCS-718
PairGain Engineering - Plant Series
Page 23
Use 12 AWG or larger wire to ensure good power connections to PG-Flex.
4
Connect the CO battery (Figure 5):
a
Connect a wire for the CO battery to TB1 BATT A (-48 Vdc) screw terminal.
b
Connect a wire for the CO battery to TB2 BATT B (-48 Vdc) screw terminal.
c
Connect the wire for the CO battery return to TB3 (BATT RTN) screw terminal.
d
Connect the CO battery return wire from TB3 on the COT Shelf to the CO battery ground
termination point.
e
Connect the CO battery wires from TB1 BATT A (-48 Vdc) and TB2 BATT B (-48 Vdc)
on the COT Shelf to the equipment bay fuse panel termination points that were selected for
this system.
Figure 5. Connecting the CO Battery