Quick Setup with CME 2
Xenus XTL User Guide
96
Copley Controls Corp.
5.6.5: Custom Digital Output Settings: Custom Event
Any of the amplifier’s digital outputs can be programmed to respond to a combination of events
including faults, warnings, and status indications. The output goes active when one or more of the
selected events take place.
5.6.5.1
Choose
Custom Event
for an output and then click
Configure Custom
to open the
Event Configuration
screen.
5.6.5.2
Select one or more of the faults described in
Fault Descriptions
(p. 35)
or any of the
following warnings or status conditions described below
.
Note that multiple functions are
OR’ed together, so any event activates the output.
Custom Events: Warnings
Warning Description
Current Limited
The current output is being limited by the I
2
T algorithm or a latched current fault
has occurred. See
I
2
T Time Limit Algorithm
(p. 153).
Voltage Limited
The current loop is commanding the full bus voltage in an attempt to control
current. Commonly occurs when the motor is running as fast as the available bus
voltage will allow.
Positive Limit Switch
Axis has contacted positive limit switch.
Negative Limit
Switch
Axis has contacted negative limit switch.
Positive Software
Limit
Actual position has exceeded the positive software limit setting.
See
Home Function
(p. 144
.
Negative Software
Limit
Actual position has exceeded the negative software limit setting.
See
Home Function
(p. 144)
Following Warning
Following error has reached programmed warning limit.
See
Following Error Fault Details
(p. 37)
.
Velocity Limit
Reached
Velocity command (from analog input, PWM input, or position loop) has exceeded
the velocity limit that was set as described in
Velocity Loop Limits
(p. 20)
.
Acceleration Limit
reached
In velocity mode, motor has reached an acceleration or deceleration limit that was
set as described in
Velocity Loop Limits
(p. 20)
.
Velocity Outside of
Tracking Window
Difference between target and actual velocity has exceeded the window.
See
Tracking Window Details
(p. 38)
.
Position Outside of
Tracking Window
The following error has exceeded the programmed value.
See
Tracking Window Details
(p. 38)
.
Continued…
Содержание Xenus XTL
Страница 1: ...Xenus XTL User Guide P N 95 00875 000 Revision 3 June 2008...
Страница 2: ...Xenus XTL User Guide This page for notes...
Страница 8: ...About this Manual Xenus XTL User Guide 8 Copley Controls Corp This page for notes...
Страница 12: ...Introduction Xenus XTL User Guide 12 Copley Controls Corp...
Страница 51: ...Xenus XTL User Guide Specifications Copley Controls Corp 51 3 24 Dimensions...
Страница 52: ...Specifications Xenus XTL User Guide 52 Copley Controls Corp...
Страница 72: ...Wiring Xenus XTL User Guide 72 Copley Controls Corp...
Страница 152: ...Regen Resistor Sizing and Configuration Xenus XTL User Guide 152 Copley Controls Corp This page for notes...
Страница 158: ...Regen Resistor Sizing and Configuration Xenus XTL User Guide 158 Copley Controls Corp...
Страница 172: ...Xenus Filter Xenus XTL User Guide 172 Copley Controls Corp...