Quick Setup with CME 2
Xenus XTL User Guide
86
Copley Controls Corp.
5.5.3: Rotary Motor Setup Parameters
View or change the settings described below. Options vary with amplifier model. Metric units are
shown here.
Setting Description
Manufacturer
Motor manufacturer’s name. Saved for reference in the motor data file.
Model Number
Motor model number. Saved for reference in the motor data file.
Units
Selects whether the parameters entered in this screen are in Metric or English units.
Motor Inertia
The rotor inertia of the motor. Used for calculating initial velocity loop tuning values. Range:
0.00001 to 4,294 kg cm
2
. Default: 0.00001 kg-cm
2.
Number of Poles
(Brushless only.) The number of magnetic poles in the motor. Required for correct
commutation of the motor. Range: 2 to 200. Default: 4.
Peak Torque
The peak torque that the motor can produce. Peak Torque divided by torque constant =
motor’s peak current limit. Range: 0.001 to 2,100 Nm. Default: 0.0001 Nm.
Continuous Torque
The continuous torque that the motor can produce. Used with the torque constant to calculate
continuous current. Range: 0.001 to 1,000 Nm. Default: 0.0001 Nm.
Velocity Limit
Maximum speed of the motor. Used to calculate the velocity and acceleration limits for the
velocity loop. Range dependent on encoder resolution.
Torque Constant
Relates the motor's input current to torque produced. Sometimes abbreviated as Kt. Range:
0.001 to 1,000 Nm/Apk. Default: 0.001 Nm/Apk.
Back emf Constant
Relates the motor's input voltage to speed. Sometimes abbreviated as Ke. Used for
calculating the maximum velocity for a given amplifier bus voltage.
Range: 0.01 to 21,000,000 V/Krpm. Default: 0.01 V/Krpm.
Resistance
Motor resistance line-to-line. Used for calculating the initial current loop tuning values. Range:
0.01 to 327 . Default: 0.01 .
Inductance
Motor inductance line-to-line. Used for calculating the initial current loop tuning values.
Range: see
Power Output
(p. 44)
.
Содержание Xenus XTL
Страница 1: ...Xenus XTL User Guide P N 95 00875 000 Revision 3 June 2008...
Страница 2: ...Xenus XTL User Guide This page for notes...
Страница 8: ...About this Manual Xenus XTL User Guide 8 Copley Controls Corp This page for notes...
Страница 12: ...Introduction Xenus XTL User Guide 12 Copley Controls Corp...
Страница 51: ...Xenus XTL User Guide Specifications Copley Controls Corp 51 3 24 Dimensions...
Страница 52: ...Specifications Xenus XTL User Guide 52 Copley Controls Corp...
Страница 72: ...Wiring Xenus XTL User Guide 72 Copley Controls Corp...
Страница 152: ...Regen Resistor Sizing and Configuration Xenus XTL User Guide 152 Copley Controls Corp This page for notes...
Страница 158: ...Regen Resistor Sizing and Configuration Xenus XTL User Guide 158 Copley Controls Corp...
Страница 172: ...Xenus Filter Xenus XTL User Guide 172 Copley Controls Corp...