Control Panel Installation
5.1
Control Panel Mounting
The Control Panel has 4 fixing holes, all of which must be used.
The Power Supply must be secured using the approved fixings below.
Please note: it is the installer’s responsibility to ensure that the
substrate to which the control panel is to be fitted is suitable and
complies with the recommendations below.
Fixing Type
Sleeve Anchor
AnkaScrew
Coach Screw
Image
Fixing Size
M4 x 40
M4 x 40
M4 x 40
Suitable For
Concrete
Brick
Concrete
Brick
Wood
Wood
Clearance must be allowed below the Control Panel for the cable connections and fuse access.
The Control Panel should be installed in a suitable location to allow maintenance but also to protect the unit
from mechanical damage or tampering.
Where the effects of fire could result in the failure or incorrect operation of the fire curtain barriers for the
appropriate fire resistance of the compartment, all electrical wiring, the drive mechanism, the control
equipment, etc. shall be rated to 300 °C or located such that it is not exposed to temperatures above its
operational rating. This is of particular importance where Emergency Retract buttons are supplied.