Use the
↑
and
↓
buttons to set the correct time to the nearest second as recorded above and press
the
OK
button to confirm the setting.
If SDD is required, add the req
uired ‘pause’ time to this figure.
7.3
Optional Settings
13)
Set Reset Mode
Use the
↑
and
↓
buttons to navigate the menu and select ‘Set reset mode’ by pressing the
OK
button.
Press the
↑
button to enable Manual Reset and the
↓
button to enable Auto Reset. Press the
OK
button to exit.
The selection of Manual or Auto reset applies to the ‘Alarm’ only. Smoke / Heat detectors
will always be Manual reset.
14)
Set Emergency Retract Hold Time
Use the
↑
and
↓
buttons to navigate the menu and select ‘EmRet top time:’ by pressing the
OK
button.
Use the
↑
and
↓
buttons to adjust the ‘pause’ time. Press the
OK
button to exit.
By default, this time is set to 5 seconds but should be increased accordingly to account
for the occupancy of the building as advised within the fire strategy. If no details have
been provided, contact the Project Manager.
15)
Double Knock
Double Knock is not available with HDD.
Double knock requires 2 active alarm signals to deploy the curtain. By default, the unit will be set to
‘Any Alarm’.
Below are the available options:
Any Alarm
Curtain will deploy immediately on activation of either the Alarm, Detector 1
or Detector 2.
Alarm and Det1
Curtain will not deploy until activation of both Alarm
AND
Detector 1.
(Detector 2 not used).
Alarm and Det2
Curtain will not deploy until activation of both Alarm
AND
Detector 2.
(Detector 1 not used).
Det1 and Det2
Curtain will not deploy until activation of both Detector 1
AND
Detector 2.
(Alarm not used).
Use the
↑
and
↓
buttons to navigate the menu and select ‘Double Knock:’ by pressing the
OK
button.
Use the
↑
and
↓
buttons to select the required operation. Press the
OK
button to confirm and exit.