Press the
↑
button to switch HDD on and the
↓
button to turn HDD off, then press the
OK
button to
exit.
The HDD function shares the SDD Drop Time to control how far the curtain deploys initially.
Set SDD drop time
Use the
↑
and
↓
buttons to navigate the menu and select ‘SDD Drop 1/10s’ by pressing the
OK
button.
Use the
↑
and
↓
buttons to adjust the drop time. The drop time is adjustable by 1/10 of a second to
give fine adjustment. Press the
OK
button to exit.
18)
Mains Fail Time
Use the
↑
and
↓
buttons to navigate the menu and select ‘Mains fail time:’ by pressing the
OK
button.
Use the
↑
and
↓
buttons to adjust the time. Press the
OK
button to exit.
The default setting is 30 minutes with a maximum setting of 240 minutes (4 hours).
This should only be changed on instruction from the Project Manager.
19)
Exit Menu
Once all settings have been input use the
↑
and
↓
buttons
to navigate the menu and select ‘EXIT
MENU’ by pressing the
OK
button.
The display will now show ‘In Auto Mode’ and display the clock.
7.4
Testing and Final Commissioning
1)
Fire Alarm Test
Test the curtain operation by having the client test the Fire Alarm. Check that any SDD or HDD
actions occur correctly.
If it is not possible to test the Fire
Alarm, disconnect the ‘Alarm’ cable from the unit.
Care must be taken when reconnecting the leads.
Incorrect connection could damage the unit.
2)
Smoke / Heat Detector Test
(If fitted)
A maximum of 2 detectors can be connected per circuit (4 total).
Use the appropriate canned smoke / heat detector testing equipment to trigger each detector.
Check that any SDD or HDD actions occur correctly.
When triggered, the detectors enter a re-checking cycle to ensure the cause of the activation has
cleared. This can take up to 5 minutes. Once clear, the unit will wait for a manual reset.