Step 4.
MARKINGS
■
Appropriate markings and/or stops should be
included on tank wall to meet customer specifications.
OPERATING INSTRUCTIONS
■
The switch can be operated 360° in either clockwise
or counter-clockwise direction.
■
When switching (with hotstick) from one position to the
next, (for example: position “A” to position “B”), the
limit plate should be located on the pin location just
beyond the position being turned to.
■
Turn hotstick until switch has fully indexed into the
next position. If for any reason, the switching
operation cannot be completed with a single motion, it
is acceptable to relax, regrip the hotstick and
complete the operation by moving the switch handle
in the
same direction
as the original effort.
NOTE: Do
not reverse the direction of the switching operation
before completing the rotation.
■
If the handle stops (jams) in a position between the
designated (marked) positions, stop switching
operation and consult the factory prior to reattempting
operation of the switch.
RTE
®
is a registered trademark of Cooper Power Systems, Inc.
4
P.O. Box 1640
Waukesha, WI 53187
#5000050062 Rev. 02
Sectionalizing Switch Installation Instructions
CAUTION: Enclosed decal (Cooper P/N
1109699A) should be displayed at or near
operating handle of switch as a warning to
service personnel. Failure to do so will
constitute a waiver of all warranty and indemnity
obligations which may be attributable to Cooper
Power Systems.
!