Step 4.

MARKINGS

Appropriate markings and/or stops should be 
included on tank wall to meet customer specifications.

OPERATING INSTRUCTIONS

The switch can be operated 360° in either clockwise 
or counter-clockwise direction.

When switching (with hotstick) from one position to the
next, (for example: position “A” to position “B”), the 
limit plate should be located on the pin location just 
beyond the position being turned to.

Turn hotstick until switch has fully indexed into the 
next position. If for any reason, the switching 
operation cannot be completed with a single motion, it
is acceptable to relax, regrip the hotstick and 
complete the operation by moving the switch handle 
in the 

same direction

as the original effort. 

NOTE: Do

not reverse the direction of the switching operation 
before completing the rotation.

If the handle stops (jams) in a position between the 
designated (marked) positions, stop switching 
operation and consult the factory prior to reattempting 
operation of the switch.

RTE

®

is a registered trademark of Cooper Power Systems, Inc.

4

P.O. Box 1640
Waukesha, WI  53187

#5000050062 Rev. 02

Sectionalizing Switch Installation Instructions

CAUTION: Enclosed decal (Cooper P/N 
1109699A) should be displayed at or near

operating handle of switch as a warning to
service personnel. Failure to do so will
constitute a waiver of all warranty and indemnity
obligations which may be attributable to Cooper
Power Systems.

!