Cooper S800-64-1 Скачать руководство пользователя страница 3

Torque requirements as defined in Table 5 shall be 
maintained.

TABLE 5
Recommended Torque

Step 2

LEAD TRAINING

Cantilever Strength of Assembly:
Sufficient to support one 500MCM Cu lead per 
contact.

Switch contacts are pre-gauged at factory and will 
have some rotation in same plane as switch blade. 
Leads attached to switch contacts must not restrict 
this rotation. The nuts holding the contacts should not 
be tightened. Leads can be bolted to rear of contact 
and care should be taken to minimize mechanical 
stress on the contacts. Standard dielectric dimensions 
for lead separation should be followed. Tight lead 
training may cause excess cantilever force and 
difficulty in switch operation.

Step 3.

INDEX PLATE

An externally installed optional limit plate prevents 
rotation to positions other than the one desired. Refer 
to Figure 4.

3

Mounting Bolts:

3/

8" diameter mounting bolts to be 

torqued 60-100 in-lbs

To Seal (Gland):

60-120 in-lbs

2.750"

(70 mm)

4.375"

(111 mm)

1.5"

(38.1 mm)

TYP.

1.325"

(34 mm)

DIA. HOLE

 .140"

(4 mm)

RAD.

 ON INSIDE WALL:

COUPLING WITH 3/8-16

TAPPED THREAD

X    .75 LG

        (19.1 mm)

 ON OUTSIDE WALL:

.312" Dia.    x      625" Long

(7.9 mm)     (15.9 mm)

WELD PIN

1.5"

(38.1 mm)

TYP.

.662"

(17 mm)

1.375"

(35 mm)

TYP.

2.187"

(56 mm)

TYP.

Figure 3.
Mounting hole and coupling placement.

NOTES:
1. Weld pins, couplings and position designations not included with switch. Pre-welded coupling pin plates available-cat. no. 2037424C02M.
2. All couplings and pins to be welded flat within an angularity tolerance of ± 30’.
3. Alternate method: weld 3/8 – 16 x 1.25 L studs in place of couplings and use .75 long spacers over studs.

OPEN

LINE A

ONLY

LINES 

A & B

LINE B

ONLY

Figure 4.
View of tank front with optional limit plate positioned over pin.

NOTE: With limit plate positioned securely as shown, switch can be operated
only counterclockwise to “line A only” position and no further.

WELD PINS (4)
(FOR 
LOCATING
LIMIT PLATE)

NOTE:  Typical position configuration shown for some “V” blade switches. 

See catalog section 800-64 for other switch layouts and schematics. 
Position labeling provided by equipment manufacturer.

Отзывы: