background image

INSTALLATION

Sectionalizing switches are sidewall or cover-mounted
in a 1.325" diameter hole with the internal electrical 
switch components completely immersed under 
transformer oil or equivalent. Refer to Figure 2 for 
dimensional information.

All parts should be inspected for damage before 
using. If there is evidence of physical damage, the 
unit should not be installed unless approved by your 
Cooper Power Systems representative.

Step 1.

MOUNT SWITCH

Switch should be mounted to four (4) couplings on 
inside of tank (refer to Figure 3 for coupling pattern) 
before tightening locking nut to sealing gland. Failure 
to do this may increase operating torque of switch or 
cause damage.

2

Sectionalizing Switch Installation Instructions

4.376"

(111.2 mm)

8.35"

(212 mm)

2.75"

(69.9 mm)

8.346"

(212 mm)

5.400"

(137.2 mm)

TYP.

.470"

(11.9  mm)

DIA. HOLE

ALL LINE

CONNECTIONS

5.153"

(130.9 mm)

.438"

(11.1 mm)

DIA. MTG. HOLES

E

A

D

C

B

.78

(20 mm)

SEE NOTE 2 AND 3

TANK SEALING
GLAND FURNISHED
WITH SWITCH

Figure 2.

Line illustration with dimensions of sectionalizing switch.

Note: 1. Dimensions given in Figure 2 and Table 3 are for reference only.

2. Handle can be used on 14 GA. (.075/1.9 mm) to .25 (6.4 mm) thick frontplate. 14 gage shown.
3. Optional padlock handle is available, but not shown.
4. See catalog section 800-64 for switch types, number of phases, and catalog numbers.

TABLE 3
Dimensional Information for Figure 2

NO. OF

A

D

E

DECKS/

SIDEWALL MOUNT

COVER MOUNT

B

C

SIDEWALL MOUNT

COVER MOUNT

SIDEWALL

COVER

PHASES

15 & 25 kV

35 kV

15 & 25 kV

35 kV

15 & 25 kV

35 kV

15 & 25 kV

35 kV

MOUNT

MOUNT

1

7.75

8.75

13.0

14.00

7.0

8.0

12.25

13.25

.745

6.0

(196.9 mm) (222.3 mm) (330.2 mm) (355.6 mm)

(177.8 mm) (203.2 mm) (311.2 mm) (336.6 mm)

(19.05 mm) (152.4 mm)

2

11.813

12.813

17.063

18.063

4.063

7.0

8.0

12.25

13.25

.75

6.0

(300.0 mm) (325.5 mm) (433.4 mm) (458.8 mm) (103.2 mm)

(177.8 mm) (203.2 mm) (311.2 mm) (336.6 mm)

(19.05 mm) (152.4 mm)

3

15.875

16.875

21.125

22.125

4.063

4.063

7.0

8.0

12.25

13.25

.75

6.0

(403.2 mm) (428.6 mm) (536.6 mm) (561.9 mm) (103.2 mm) (103.2 mm) (177.8 mm) (203.2 mm) (311.2 mm) (336.6 mm)

(19.05 mm) (152.4 mm)

Sealing is accomplished with O-rings on operating 
shaft and gasketed sealing gland secured on outside 
of tank with locking nut.

Switch should be located to ensure recommended 
clearances in Table 4 are maintained.

TABLE 4
Recommended Clearances

Mechanical

External handle clear of obstruction. Clearances also required
for hook-stick operation.

Dielectric (Under Oil)

Minimum of 4 inches on all sides of the switch.

Отзывы: