S280-70-10
29
FORM 6-LS CONTROL
REMOTE
BOX
Not All Remote
Connections
Shown
SHIELD
12 CO1
3
5
7
4
6
8
CI1
CI2
CI3
CI1
CI2
CI3
Remote
Trip and
Lockout
Supervisory
Trip and
Lockout
Supervisory
Close
TB1
1
2
+
—
Whetting Voltage Terminals
Customer Wiring
Customer Wiring
28 VDC
11
13
CO1
Recloser
Status
A*
B*
*Contacts shown
with recloser in
OPEN position.
Factory-Supplied
28 VDC Whetting
Voltage
A Single common wire can be used for multiple inputs
if it is jumpered at the I/O board terminals.
NOTES:
Arresters to be metal oxide varistors (MOVs) 320 VAC,
150 Joules or equivalent.
Shielding for Supervisory Cables should follow
the representative input control contacts and
output status contacts as shown.
External lead resistance must not exceed 200 ohms.
Supervisory and Remote Functions are
default functions.
TB9
Figure 19.
Shielding and Surge Protection for Supervisory and Remote Cables.