Standard Default Supervisory Input
Control and Output Status Contacts
Standard customer connections TB1 and accessory
customer connections are TB3 and TB4. Refer to Figures
17 and 18 and Tables 4, 5, and 6. The Idea Workbench
allows customization of all the control and status points.
Refer to
Service Information S280-70-4 (ProView 4.X.X) or
S280-70-21 (ProView 5.X.X) Form 6 Microprocessor-
Based Recloser Control Programming Guide
for additional
information.
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
26
Contact
Input Voltage
Rating
120 VAC
8 A
12 VDC
8 A
24 VDC
8 A
48 VDC
1 A
125 VDC
0.4 A
TABLE 5
Ratings Table for Output Status Contacts CO1
through CO12
(Resistive Load – Pickup Time 8 ms, Dropout 15 ms)
Contact
Input Voltage
Rating
120 VAC
8 A
12 VDC
8 A
24 VDC
8 A
48 VDC
8 A
125 VDC
8 A
TABLE 6
Ratings Table for Output Status Contact SS1
(Resistive Load – Pickup Time 2 ms, Dropout 15 ms)
IMPORTANT
Shielding and Surge Protection of
Supervisory Cables
All supervisory operation and control monitor leads must
be protected within shielded cables. Refer to Figure 19.
NOTICE:
External leads must be shielded and the shield
must be grounded at both ends. Terminate each lead
with a 320VAC, 150 Joules metal oxide varistor (MOV),
or equivalent, at the remote end. Attach MOV’s between
the leads and ground. Failure to properly shield and
protect leads can result in equipment damage and/or
unintentional operation.
Nominal Minimum
Input Voltage
Current
Operating Time
12 VDC – 250 VDC,
120/240 VAC
2.5 mA
5 milliseconds
TABLE 4
Operating Current Requirements for Standard and
Optional Supervisory Inputs