Installing the IPC-8000
Installation Instructions: IPC-8000
P/N P10-00059 Rev A
I
N
S
T
A
L
L
A
T
I
O
N
I
N
S
T
R
U
C
T
I
O
N
S
7
1.
Ensure the AC power source is off.
2.
Identify or cut the following penetration holes. Refer to
hole locations on the top and sides of the enclosure.
a.
AC Power Cord
b.
Network Cable (if required)
c.
RF Antenna Cable (if required)
Table 3 Conduit Hole Size and Flat Surface
Trade Size of Conduit
Recommended Diameter of
Opening
Recommended Minimum
Diameter of Flat Surface
Inches
mm
Inches
mm
Inches
mm
0.375
9.53
0.709
18
0.98
25
0.5
12.70
0.866
22
1.20
30
0.75
19.05
1.10
28
1.50
38
1
25.4
1.38
35
1.90
48
1.25
31.75
1.73
44
2.40
60
1.5
38.10
1.97
50
2.60
67
2
50.80
2.48
63
3.30
83
6.2.2 Connecting External AC Power Cable
When routing the external AC power, take care to allow for the following:
Follow best practices for proper separation of the AC power cable, RF Antenna
cable and Ethernet cable to avoid RF interference.
Installation of a NEMA-rated conduit and fitting.
All conduit and cables inserted into the enclosure shall adhere to the
Local Codes and per the Authority having jurisdiction.
Connect to an AC circuit protected by a maximum 20 AMP fuse or circuit
breaker. A readily accessible disconnect device must be provided.