10. Install the CID101 corrosion inhibitor device included with kit by peeling back the

protective covering to expose the adhesive.  Install the CID101 in upper portion inside

enclosure wall.

REMOVAL OF EXISTING CIRCUIT ASSEMBLY
(For units made AFTER October, 2005).

1. Disconnect branch AC power at circuit

breaker and lockout.

2. Disconnect DC power by turning

designated disconnect key or selector

switch to "OFF".

3. After removing all AC and DC power to

the fixture, remove all cover fasteners

to gain access to the interior.

4. Disconnect wire leads at the pilot light and test button and remove the four (4) 1/4-20

screws and lock washers on the aluminum backplate.  Remove the old interior

assembly and set aside.  

5. Disconnect all incoming connections from the terminal block and terminals L+ and L-

from the circuit board.

6. For units made before September 2012, only disconnect all incoming connections

from terminals GND through L-.

7. Install the new interior assembly inside your existing enclosure using the same four (4)

1/4-20 screws and lock washers removed in Step 4.

8. Replace pilot light LED with new LED provided.

9. Make all wiring connections following the wiring diagram located in the new assembly

(also see Figure 1).

10. Install the CID101 corrosion inhibitor device included with kit by peeling back the

protective covering to expose the adhesive.  Install the CID101 in upper portion inside

enclosure wall.

CONNECT AC POWER AND TEST SYSTEM

1. Test wiring for correctness with continuity checks and also for unwanted grounds with

insulation resistance tester. 

2. Close cover and securely tighten all cover bolts and nuts to 30 ft.-lbs. torque, making

certain that no cover bolts are omitted.

3. Connect AC power and allow ELPS system to charge for 72 hours before conducting

any tests.  Do not disconnect AC power or depress the "Push-To-Test" button until the

unit is fully charged.  The LED indicator lamp will illuminate steadily (no blinking) when

the ELPS is fully charged.

4. Test the emergency lighting system for proper operation.  Turn on the designated

disconnect switch and observe: "Main Power ON" indicating light should be "ON" and

the EVLA12 emergency light(s) should be "OFF".

5. Press the "Push-To-Test" indicating push button switch and observe: "Main Power ON"

light should be "OFF" and the EVLA12 emergency light(s) should be "ON".

6. Lock the designated disconnect switch "ON" to prevent unauthorized persons from

turning system "OFF".

7. Conduct periodic testing as outlined in Instruction Manual IF 1072 (before October,

2005) and IF 1510 (after October, 2005) as supplied with the unit when originally

installed.

Assistance may also be obtained through your local Crouse-Hinds Sales Representative

or the Crouse-Hinds Service Center, P.O. Box 4999, Syracuse, NY 13221, Phone 315-

477-5531.

Part Number

Interior Assembly            ELPS K50

Place these instructions (in protective plastic envelope provided) in a safe, convenient

location attached to or near the emergency lighting fixture.

MAINTENANCE

1. Conduct periodic testing in accordance with local authority and Periodic Testing

section of these instructions.

2. Clean fixture lens and exterior surfaces periodically.  We recommend every three (3)

months or more frequently, if appropriate.

3. Frequent interior inspection should be made.  A schedule for maintenance check

should be determined by the environment and frequency of use.  It is recommended
that it should be at least once a year.

4. Perform visual, electrical, and mechanical checks on all components on a regular

basis.

• 

Visually check for undue heating evidenced by discoloration of wires 
or other components, damage or worn parts, or leakage evidence by 
water or corrosion in the interior.

• 

Electrically check to make sure that all connections are clean and tight.

• 

Mechanically check that all parts are properly assembled.

5. Do not attempt field replacement or repair of ELPS50 power supply cover gasket.

Instead, remove damaged gasket and continue to use cover without gasket.  This will
assure safety for use in Class I and Class II hazardous (classified) locations.
However, the enclosure will not be raintight. 

WARNING

To avoid explosion, do not damage the flat joint surfaces.  Do not use hammers or 

prying tools to open covers.  Do not handle covers roughly, or place them on 

surfaces that might damage or scratch the flat joint surfaces.

TABLE 1

Wire Sizing for Remote Installation

(for copper wire)

Running Distance* (ft.) Between Power Supply and Remote Lighting Fixture

Ambient Temp. ºC

25

40

55

Lighting Fixture
Load-Max. Watts

12

24

30

12

24

30

12

24

30

Wire Size
•  14 AWG

125

63

50

117

58

47

109

55

44

•  12 AWG

198

99

79

185

92

74

173

87

69

•  10 AWG

317

158

127

295

148

118

276

138

110

•  8 AWG

505

253

202

471

235

188

440

220

176

Maximum distance to limit line voltage drop to 5%

.

Figure 3

NOTE

Older circuit boards are wired to normally closed contacts.  Replacement circuit 

boards must be wired to normally open contacts.

CAUTION

To avoid explosion, clean both flat joint surfaces of body and cover before closing.
Dirt or foreign material must not accumulate on flat joint surfaces.  Surfaces must
seat fully against each other to provide a proper explosionproof seal.

WARNING

To avoid explosion always disconnect primary power source using designated
disconnect switch before opening enclosure for inspection or service.

IF 1510-A  •  09/12

Copyright © 2012, Cooper Industries, Inc.

Page 2

Содержание ELPS LIGHT-PAK ELPS-K50

Страница 1: ...D in the pilot light and replace with the new 2 volt LED supplied with the new interior assembly 9 Make all incoming wiring connections following the wiring diagram located in the new assembly also se...

Страница 2: ...when originally installed Assistance may also be obtained through your local Crouse Hinds Sales Representative or the Crouse Hinds Service Center P O Box 4999 Syracuse NY 13221 Phone 315 477 5531 Part...

Страница 3: ...2 Cooper Industries Inc Supercedes 12 10 TROUBLESHOOTING GUIDE SYMPTOM 1 LED does not light 2 LED is blinking twice 3 After 72 hours unit is not fully charged LED steady and lamp heads flash 4 LED is...

Страница 4: ...r s plus t t l TAPE 6 8 Retirer l ancienne ampoule incandescente ou DEL de la lampe t moin et la remplacer par la DEL neuve de 2 volts fournie avec le module interne neuf 9 Refaire toutes les connexio...

Страница 5: ...sont fournis l origine avec l appareil Il est aussi possible d obtenir un soutien technique aupr s de votre repr sentant r gional des ventes Crouse Hinds ou du service apr s vente l adresse suivante C...

Страница 6: ...clignote deux fois 3 L appareil n est pas pleine charge apr s 72 heures DEL illumin et les luminaires clignotent 4 La DEL clignote trois fois SOLUTION 1a V rifier l alimentation du luminaire 1b V rif...

Страница 7: ...r nuevo 9 Realice todas las conexiones de cables entrantes de acuerdo al diagrama de cableado incluido en el ensamble nuevo vea tambi n la Figura 1 y reconecte las puntas de los cables de los accesori...

Страница 8: ...lmente Tambi n puede obtener asistencia a trav s de su representante de ventas local Crouse Hinds o el centro de servicios de Crouse Hinds P O Box 4999 Syracuse NY 13221 tel fono 315 477 5531 N mero d...

Страница 9: ...a LED parpadea dos veces 3 Luego de 72 horas la unidad no est cargada LED constante y las cabezas de la l mpara brillan 4 La LED parpadea tres veces SOLUCI N 1a Verifique que llegue energ a al accesor...

Отзывы: