Jumpers
The jumpers are located on PCB100. See
Figure 1-1 for the location of the jumpers.
The jumpers, when cut, configure the
PCB100 Control Board to have the
following functions:
•
JP2 — RES PEC - Cut to allow the use
of the PEC 510 resistive photocell.
•
JP5 — FAILCLOSE - Cut to allow
sensing of closed contacts as an alarm
signal from an external red light
controller.
•
JP6 — DAYINHIBIT - Cut to turn off
day flashing for the unit.
•
JP7 — DUAL - Cut to allow dual
system operation: it inhibits white light
flashing at night. A dual system is one
that flashes only white lights during
the day and flashes only red lights at
night. Dual systems may have white
light backup at night in the event of a
red light failure. JP7 is applicable only
to systems that use an external red
light controller.
•
JP8 — CAT - Cut to allow catenary
operation, flashing the structure lights
at sixty flashes per minute in a middle-
top-bottom sequence.
•
JP9 — 50HZ - Cut to allow operation
at 50HZ.
Normal Operation
The following conditions prevail during
normal operation when all beacons are
flashing:
•
All LED indicators in the Tier and
Beacon Display that have
programming switches closed are
GREEN.
•
The ALARM LED is off.
•
The CONTROL SWITCH is in
AUTO.