CIRCULATING AIR SOURCE WATER HEATER INSTRALLATION
20
1.5 Installation of Water Circulating System
1) Design and construction of water system must accord with relative standard and
requirements.
2) The unit adopts target flow switch for cut-off protection. Point of zero flow has been set in
factory.
3) Confirm pipe diameter of water inlet/outlet pipe according to rated flow volume and
recommended flow speed of the unit to reduce resistance loss. Flow speed of hot water pipe
can be chosen from the table below.
Recommended flow speed of hot water pipe
Nominal diameter
-
mm
.
15-20
25-40
≥50
Flow speed
-
m/s
.
≤0.8
≤1.0
≤1.2
4) During connection of water pipe, separately connect the two pieces of attached PPR pipes
with water inlet and outlet of the unit and then connect them with external water pipe.
5) Water pipe and valve: In order to ensure cleanness of water system, PVC and PPR pipes are
usually adopted. Galvanized pipe be internal-external galvanized and hot dipped. Cut-off
valve, ball valve, check valve, shut-off valve and so on in common use should adopt copper
core. Raw rubber tape should be used at the place between valve and connection pipe for
thread sealing. Don’t use other types like crude fiber for sealing to avoid pollution to pipeline.
6) Layout of water pipe should be level and vertical and does not bend as much as possible to
reduce resistance loss of water system.
7) Water pipe must be insulated with polythene foam, glass cotton etc. to avoid heating loss.
Содержание GRS-Cm18/A-M
Страница 1: ...CIRCULATINGAIR SOURCE WATER HEAT PUMP SERVICE MANUAL...
Страница 3: ...C H COMMERCIAL AIR CONDITIONERS CIRCULATING AIR SOURCE WATER HEATER 1 PRODUCT...
Страница 9: ...C H COMMERCIAL AIR CONDITIONERS CIRCULATING AIR SOURCE WATER HEATER 7 CONTROL...
Страница 10: ...CIRCULATING AIR SOURCE WATER HEATER CONTROL 8 UNITS CONTROL 1 OPERATION FLOWCHART...
Страница 16: ...C H COMMERCIAL AIR CONDITIONERS CIRCULATING AIR SOURCE WATER HEATER 14 INSTALLATION...
Страница 30: ...AIR COOLED SCROLL CHILLER MAINTENANCE 28 MAINTENANCE...
Страница 34: ...AIR COOLED SCROLL CHILLER MAINTENANCE 32 2 FLOW CHART OF TROUBLESHOOTING 1 High pressure protection E1...
Страница 35: ...AIR COOLED SCROLL CHILLER MAINTENANCE 33 2 Low pressure protection E3...
Страница 36: ...AIR COOLED SCROLL CHILLER MAINTENANCE 34 3 Compressor overload protection E5...
Страница 37: ...AIR COOLED SCROLL CHILLER MAINTENANCE 35 4 Discharge high temperature protection E4...
Страница 38: ...CIRCULATING AIR SOURCE WATER HEATER MAINTENANCE 36 5 Water flow switch protection Ec...
Страница 39: ...AIR COOLED SCROLL CHILLER MAINTENANCE 37 6 Water level switch error L2 7 Communication failure E6...
Страница 51: ...AIR COOLED SCROLL CHILLER MAINTENANCE 49 5 EXPLODED VIEWS AND PART LIST GRS Cm18 A M Part List...
Страница 54: ...AIR COOLED SCROLL CHILLER MAINTENANCE 52...