Air Source Heat Pump Water Heater
31
Pressure gauge
Low pressure valve
High
pressure
valve
Fluoride injection
mouth
Fluid pipe
Fluid valve
Hex key
Air pipe
Air valve
Injection
hoses
Refrigerate bottle
Figure 12-1 Refrigerant replenishment diagram
Fluoride injection
mouth
Fluid pipe
Fluid valve
Hex key
Air pipe
Air valve
Figure 12-2 Refrigerant discharging diagram
13 Method for Refrigerant Reclamation
Refrigerants can be reclaimed for the source water heater only in specific mode.
In normal hot water mode, press and hold MODE+
for 5 seconds to enter the
query status. When the temperature display area displays 00, press and hold
MODE+
for 5 seconds. Then, 00 changes to P0. Press the
or
button to
switch to the P3. Then, press the MODE button for settings. Press the
or
button
again to change 00 in the time display area to 01. Press MODE to enter the
defrosting mode, and complete the settings for refrigerant reclamation settings. After
the settings are complete, first close the fluid valve (smaller valve), and when the
there is cold air blowing out from the outlet, immediately close the air valve (larger
valve). After it is closed, immediately shut down the unit
Caution
Refrigerant reclamation must be promptly completed, so as not to cause any