Revised: 01/09/2016 13/02/17
11
Rear vent Flue Installation
1. Determine the exact location for the heater.
2.
Mark the exact location for the wall penetration
a.
Determine that you will not be cutting through any vertical wall studs.
b.
Check that the location of the wall-mounted terminal conforms to the
requirements of AS/NZS 5601 – Location of a Flue Terminal.
3.
Cut 2 holes 70mm in diameter at 160mm centres holes to be side by side in the
horizontal.
4.
Use the back of the cowl as a template for fixing holes.
5.
Fit flex flue to spigots on the rear of the cowl using provided hose clamps and seal
with silicone.
NOTE- it may be necessary to trim the flue depending on wall thickness.
6. Attach the back of the cowl to the wall. Silicone around outside.
I
NSTALLATION - GAS PRESSURE TO GAS VALVE
NAT 1.1 KPA / LPG 2.75 KPA
Inbuilt & Freestanding Models
Only to be carried out by an authorised person!
1.
Unpack flue kit and log set. (Packed inside with heater).
2.
Carefully remove the cardboard carton surrounding the heater then remove the heater
from the pallet.
3.
Remove louver panel by undoing 2 screws located each side of the panel. Unclip
connection to circuit board gently, by squeezing plug.
4.
Connect flue pipes to unit. Connect gas to gas valve and check pressure coming in.
Minimum pressure required – NAT GAS = 1.1 KPA & LPG = 2.75KPA. High and low
settings on gas valve are factory set and should be correct (refer to page 4 for Pressure
Settings). Check these settings are correct, and adjust if necessary.
5.
ACCESS – FREESTANDING MODEL
To access fire box, remove 1 self-tapping screw on underside front of each panel. Pull the
bottom of the side panel away from the heater and unclip 4 locking brackets.
6.
ACCESS – INBUILT MODEL
To access fire box, the heater needs to be approximately 100mm out from its final
position. Remove bottom panel by undoing 2 screws, one on the left and one on the right.
Slide fascia panel up and remove.
Undo the 2 screws on top and bottom of front side panels, 2 on the left and 2 on the right.
Unclip H locking brackets and remove door.
7.
Manually start by pressing top button. Top & bottom light will come on and heater will
not light for approx 1 minute. Once the firebox gets warm the middle light comes on the
NOTE: AIR INTAKE RESTRICTOR PLATE MUST BE REMOVED
FOR FLUE LENGTHS OF MORE THAN 1 METER.
Содержание grange
Страница 15: ...Revised 01 09 2016 13 02 17 15 6mm Cement Sheeting required for floor installation ...
Страница 19: ...Revised 01 09 2016 13 02 17 19 INTERNAL WALL UNDER FLOOR INSTALL WITH HORIZONTAL FLUE ...
Страница 21: ...Revised 01 09 2016 13 02 17 21 DIMENSIONS OF APPLIANCE INBUILT MODEL ...
Страница 23: ...Revised 01 09 2016 13 02 17 23 FREESTANDING MODEL Overall height on the freestanding model is 770mm ...
Страница 25: ...Revised 01 09 2016 13 02 17 25 WIRING DIAGRAM PRESSURE SWITCH ...
Страница 32: ...Revised 01 09 2016 13 02 17 32 ...