background image

 Revised: 23/08/2012 

 

Printed 

13

Printed: 20/03/2013 

 
 
Installation in a Stud wall cavity. 
 

1.

 

Mark the exact location of where the heater is to be located with an outline 
720mm wide by 615mm high 

2.

 

Check that location for the flue terminal conforms to the requirements of AS/NZS 
5601 Location of a Flue Terminal. 

3.

 

Cut out the plaster board and timber supports  (re-position supports if necessary) 

4.

 

Refer to figure 1, and continue as described on previous page. 

5.

 

When completed, fit the “console cover” supplied to the heater fascia surround. 
Fit to the heater body. Attach heater fascia. 

 

Installation through the wall. 

 

1.

 

Mark the exact location of where the heater is to be located with an outline    
720mm wide by 615mm high. 

2.

 

Check that location for the flue terminal conforms to the requirements of AS/NZS 
5601 

      Location of a Flue Terminal. 
3.

 

Cut out the plasterboard and timber supports (re-position if necessary). Cut out 
the outer brickwork. 

4.

 

Fit the bends and the short inner and outer to the heater spigot  

5.

 

Feed the gas line through the hole located at the lower right hand side of the outer 
weather cover (provided) and the flue pipes through the pre-punched hole for the 
flue pipes on the upper left hand side. 

6.

 

Locate the appliance, connect gas. 

7.

 

Fit the outer weather cover over the exposed heater body and screw to the outer 
wall. Also use a silicon sealant. 

8.

 

Trim the inner flue to 50mm longer than the outer flue. 

9.

 

Fit the cowl backing plate to the outer weather cover (Also use a silicon sealant). 

10.

 

Fit the cowl to the flue pipes and then to the cowl mounting plate. 

11.

 

Firmly fix the appliance in to position using the brackets on each side of the 
heater casing. 

12.

 

Replace fascia surround and Fascia. 

 

External weather cover assembly/installation. 
 

The weather cover is supplied partially assembled with only the base panel to be attached to 
complete the assembly (screws provided) 
 
There is a moveable cover plate at the lower right hand of the rear panel for fitment of the gas 
connection. 
 
The horizontal cowl mounting plate (which is common for both full and partial wall 
penetrations) has a total of 8 pre-drilled holes. For attachment to the external weather cover, 
the 4 inner 4.5 mm holes are utilized (screws provided). When attached to masonry or 
weatherboard the 4 outer 6mm holes are utilized. 

 

Note: when the weather cover and cowl are attached it is necessary to seal the top and side 
edges with silicone to prevent water entry.

 

 
 
 
 

Содержание CONSOLE

Страница 1: ...OPERATING INFORMATION INSTALLATION INSTRUCTIONS Serial Number of Heater ____________ Model ___________________ Hermitage Gas Heaters ARE AUSTRALIAN OWNED MANUFACTURED BY SHAMIC SHEETMETAL SHAMIC SHEE...

Страница 2: ...vel surface Inbuilt models must be placed on AC sheeting to prevent unit from rattling Heater must be checked for scratches or dents prior to installation All glass must be fitted with a screw driver...

Страница 3: ...4 CUSTOMER OPERATING INSTRUCTIONS 6 SAFETY PRECAUTIONS SAFETY FEATURES 7 INSTALLATION INSTRUCTIONS 8 14 LOG INSTALLATION WIRING DIAGRAM 15 GAS VALVE ADJUSTMENT 16 TROUBLESHOOTING GUIDE 17 DIMENSIONS W...

Страница 4: ...al Conform to AS3100 240V 50 Hz 120 Watts Max Air Pressure Switch Aria 380 series 5471 Cut in Pressure 45 Pa Cut out Pressure 40 Pa Electrical Connection Standard Flex 2 Mt 3 Pin Plug Hermitage Freest...

Страница 5: ...n accordance with AS NZS 5601 Gas Installation Standard Manufacturer s Installation Instructions Local Gas Fitting Regulations Municipal Building Codes This appliance must only be installed and servic...

Страница 6: ...ion Note At start up if the High position has been selected the heater will only ignite on the Low setting and will automatically switch to the High setting after an initial warm up period TURNING THE...

Страница 7: ...rized person who is responsible for its correct operation at the time of installation AS NZS 5601 Appliance Commissioning 9 2 The commissioning of an appliance shall take full account of special desig...

Страница 8: ...and adjust if necessary J Reassemble heater in reverse order of above connect electrical cord to correctly wired and earthed 240 volt AC power point K Operate heater check operation of heater on both...

Страница 9: ...lly over the hole 6 Fit the tapered flue dress trim wide end towards the heater over the flue outlet on top of the heater 7 Fit the inner and outer 900mm flue lengths to spigots on top of the heater 8...

Страница 10: ...surround The fascia is secured to the heater surround by 2 lugs and can be removed by lifting the fascia upward approximately 5 mm and then forward 4 Remove the 2 screws holding the fascia surround to...

Страница 11: ...nd the exhaust port at the flue terminal 2 Feed both flexible pipes down the flue cavity 3 Fix flue terminal securely to top of flue cavity and seal to prevent water entry Seal with Hi Temperature wat...

Страница 12: ...gas connection 3 Connect Gas 4 Fit the bends and short inner and outer flue pipes to the heater spigot 5 Slide the heater into position with the flue pipes protruding through the hole in the rear of t...

Страница 13: ...e flue pipes through the pre punched hole for the flue pipes on the upper left hand side 6 Locate the appliance connect gas 7 Fit the outer weather cover over the exposed heater body and screw to the...

Страница 14: ...Printed 20 03 2013 IMPORTANT The Hermitage Gas Log Heater must always be vented to the outside IMPORTANT Cut outer flue casing to ensure inner Flue exhaust pipe protrudes 50 mm above outer casing Cri...

Страница 15: ...as illustrated below to the pins located on the front and rear logs Logs should not touch the sensor or sparker Above diagram shows correct orientation of logs WIRING DIAGRAM GAS VALVE ADJUSTMENT The...

Страница 16: ...e nut clockwise to increase gas pressure Natural Gas Burner test point pressure HIGH 0 9 kPa LOW 0 48 kPa Primary air shutter adjustment fully open Freestander fully open Inbuilt Natural gas injector...

Страница 17: ...ed start and will not start until unit warms up Check wiring Install fan in correct location Remove and clean fan Unit cuts out after a period of time then cycles on and off See Room fan not operating...

Страница 18: ...ve base 250mm from right side of unit How to Make a Warranty Claim Coonara Heatcharm Arrow and Settler Heaters The full Warranty Statement for your heater is contained in the Installation and Operatin...

Страница 19: ...ressly excludes any liability hereunder for defects or damage caused by the installation or of any components not expressly authorised and approved by Shamic Shamic further assumes no liability for de...

Страница 20: ...service and check be made by a qualified person annually The fascia should be removed and the fan vacuumed annually To clean the appliance simply wipe over with a damp cloth Do not use solvents or abr...

Страница 21: ...____________________________ ADDRESS __________________________________________________________________________________________________ CITY STATE POSTCODE ____________________________________________...

Отзывы: