UMD V3 Installation Manual - Remote Control
13 November 2018
Page
14
of
39
Advanced Controller:
1.
The Advance controller requires the
‘Third Party Protocol’ to be programmed into the controller using
a ‘Data
Configuration
Card’. The
controller is the
n enabled using the ‘Reefer Manager’ PC application.
Scroll through the options and s
et the ‘Communications Protocol’ to ‘OTHER’.
2.
Note: Minimum Firmware Revision for the Micro should be: 04.12
Picture 11: Carrier Datacard in Controller PCMCIA Slot
Powering Up the System for the First Time:
After all hardware and wiring is installed, power may be connected to the Cooltrax System for the first time.
IMPORTANT NOTE:
Verify that all cable and individual wiring connections are properly connected and weather-sealed before
reconnecting the cable to the positive terminal first and then to the negative terminal of the reefer battery.
Once the cables to the positive and negative terminals of the refrigerated battery are connected, the UMD will
commence its power up sequence.
Boot-Up Sequence:
1.
Within approximately 30 seconds the UMD ‘Power’ LED will light up GREEN, followed closely by the
battery light.
2.
Shortly after the Signal LED will begin to flash, assuming that there is GPRS or 3G service available on
the GSM/3G network.
3.
The IP LED will at first flash and then remain in a constant ON State once an IP connection has been
established
4.
The GPS LED will light up a constant RED to indicate that GPS has been acquired
–
typically in 30 secs
or less.
5.
If RF Tags have been installed then the RF LED will flash every few seconds as the tags communicate
with the RF Reader section of the UMD