4 Modbus/TCP
Ethernet Option Board /
700.002 735 AE01
4-9
4.6.3
Energy Counter 30201 – 30203
The last number of the 'Format' field indicates the decimal point place in the 'Energy' field.
If the number is bigger than 0, move the decimal point to the left by the number indicated. For example,
Energy = 1200, Format = 52. Unit = 1. Energy = 12.00kWh
Address
Purpose
30201
Energy
30202
Format
30203
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 4-19: Energy Counter
4.6.4
Reset table Energy Counter 30301 – 30303
Address
Purpose
30301
Energy
30302
Format
30303
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 4-20: Reset table Energy Counter
4.6.5
Error History 30401 – 30417
The error history can be viewed by reading from the address 30401 onward. The errors are listed in
chronological order so that the latest error is mentioned first and the oldest is mentioned last. The error history
can contain 16 errors at any time. The error history contents are represented as follows.
Error code
Sub-code
Value as a hexadecimal
Value as a hexadecimal
Table 4-21: Error Coding
For example, the IGBT temperature error code 41, sub-code 00: 2900Hex -> 4100Dec. For complete list of
error codes please see frequency converter’s manual
Содержание 700.002 735
Страница 1: ...Ethernet Option Board LV7000 Order No 700 002 735 Issue 06 08 AE01 Operating Manual ...
Страница 8: ...Contents Ethernet Option Board 700 002 735 AE01 ...
Страница 10: ...1 Introduction 1 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 14: ...2 Ethernet Board Technical Data 2 4 Ethernet Option Board 700 002 735 AE01 ...
Страница 20: ...3 Installation 3 6 Ethernet Option Board 700 002 735 AE01 ...
Страница 30: ...4 Modbus TCP 4 10 Ethernet Option Board 700 002 735 AE01 ...
Страница 32: ...5 Start up Test 5 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 34: ...6 Error Codes and Errors 6 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 37: ......