6 Error Codes and Errors
Ethernet Option Board /
700.002 735 AE01
6-1
6
Error Codes and Errors
6.1
Frequency Converter Error Codes
To make sure that the board functions are correctly in all circumstances and that no errors occur, the board
set the fieldbus error 53 if it doesn't have a functional connection to the Ethernet network or if the connection
is faulty.
In addition, the board assumes that there is always at least one functional connection after the first
Modbus/TCP connection. If this is not true, the board will set the fieldbus error 53 in the frequency converter.
Confirm the error by pressing the 'reset' button.
Card slot error 54 may be due to a faulty board, a temporary malfunction of the board or a disturbance in the
environment.
6.2
Modbus TCP
This section discusses Modbus/TCP error codes used by the OPT-CI board and possible causes of the errors.
Code
Modbus exception
Possible cause
0x01
Illegal function
The appliance does not support the function
0x02
Illegal data address
Attempt to read the query over the memory
range
0x04
Slave device failure
The appliance or connections are faulty
0x06
Slave device busy
Simultaneous query from two different masters
to the same memory range
Table 6-1: Error Codes
Содержание 700.002 735
Страница 1: ...Ethernet Option Board LV7000 Order No 700 002 735 Issue 06 08 AE01 Operating Manual ...
Страница 8: ...Contents Ethernet Option Board 700 002 735 AE01 ...
Страница 10: ...1 Introduction 1 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 14: ...2 Ethernet Board Technical Data 2 4 Ethernet Option Board 700 002 735 AE01 ...
Страница 20: ...3 Installation 3 6 Ethernet Option Board 700 002 735 AE01 ...
Страница 30: ...4 Modbus TCP 4 10 Ethernet Option Board 700 002 735 AE01 ...
Страница 32: ...5 Start up Test 5 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 34: ...6 Error Codes and Errors 6 2 Ethernet Option Board 700 002 735 AE01 ...
Страница 37: ......