background image

GB

56

Lighting Instructions

Chimney

In order for the stove to perform satisfactorily the chimney height must 
be sufficient to ensure an adequate draught of approximately 15 Pa so as 
to clear the products of combustion and prevent smoke problems into the 
room. 

NOTE: A chimney height of not less than 4.5 metres measured vertically 
from the outlet of the stove to the top of the chimney should be satisfacto-
ry. Alternatively the calculation procedure given in EN 13384-1 may be used 
as the basis for deciding whether a particular chimney design will provide 
sufficient draught. BS EN 15287-1:2007 gives additional details.

The outlet from the chimney should be above the roof of the building in ac-
cordance with the provisions of Building Regulations Approved Document J.

If installation is into an existing chimney then it must be sound and have 
no cracks or other faults which might allow fumes into the house. Older 
properties, especially, may have chimney faults or the cross section may 
be too large i.e. more than 230 mm x 230 mm. Remedial action should be 
taken, if required, seeking expert advice, if necessary. If it is found neces-
sary to line the chimney then a flue liner suitable for solid fuel must be used 
in accordance with Building Regulations Approved Document J.

Any existing chimney must be clear of obstruction and have been swept 
clean immediately before installation of the stove. If the stove is fitted in 
place of an open fire then the chimney should be swept one month after 
installation to clear any soot falls which may have occurred due to the dif-
ference in combustion between the stove and the open fire.

If there is no existing chimney then any new system must be to the designa-
tion described above and in accordance with Building Regulations Approved 
Document J.

A single wall metal fluepipe is suitable for connecting the stove to the 
chimney but is not suitable for use as the complete chimney. The chimney 
and connecting fluepipe must have a minimum diameter of 150 mm and its 
dimension should be not less than the size of the outlet socket of the stove.

Any bend in the chimney or connecting fluepipe should not exceed 45°.  
90° bends should not be used. Combustible material should not be located 
where the heat dissipating through the walls of fireplaces or flues could 
ignite it. Therefore when installing the stove in the presence of combustible 
materials due account must be taken of the guidance on the separation of 
combustible material given in Building Regulations Approved Document J 
and also in these stove instructions.

If it is found that there is excessive draught in the chimney then a draught 
stabiliser should be fitted. Fitting of a draught stabiliser will affect the 
requirement for the permanent air supply into the room in which the stove 
is fitted in accordance with Approved Document J (see also combustion air 
supply).

Adequate provision e.g. easily accessible soot door or doors must be 
provided for sweeping the chimney and connecting fluepipe where it is not 
intended for the chimney to be swept through the appliance.

hearth

The hearth should be level and able to accommodate the weight of the stove 
and its chimney if the chimney is not independently supported. The weight 
of the stove is indicated in the brochure.

The stove should preferably be installed on a non-combustible hearth of a 
size and construction that is in accordance with the provisions of the cur-
rent Building Regulations Approved Document J.

The clearance distances to combustible material beneath, surrounding or 
upon the hearth and walls adjacent to the hearth should comply with the 
guidance on the separation of combustible material given in Building Regu-
lations Approved Document J and also in these stove instructions.

If the stove is to be installed on a combustible floor surface, it must be co-
vered with a non-combustible material at least 12mm thick, in accordance 
with Building Regulations Approved Document J, to a distance of 30 cm in 
front of the stove and 15 cm to each side measuring from the door of the 
combustion chamber.

Combustion air supply

In order for the stove to perform efficiently and safely there must be an 
adequate air supply into the room in which the stove is installed to provide 
combustion air. The provision of air supply to the stove must be in ac-
cordance with current Building Regulations Approved Document J. Special 
attention should be taken in newer build properties where the design air 
permeability is less than 5m3/h.m2. Approved Document J gives more infor-
mation on this. An opening window is not appropriate for this purpose.

The fitting of an external air kit direct to outside air must not be con-
sidered substitute for installing the appliance with a permanently open 
air vent in compliance with ventilation requirements stated in Approved 
Document J. Please reference ADJ for further guidance.

Connection to chimney

Stoves may have a choice of either a rear or top flue gas connector that 
allows connection to either a masonry chimney or a prefabricated factory 
made insulated metal chimney in accordance with their instructions. In 
some cases it may be necessary to fit an adaptor to increase the diameter 
of the flue to the minimum required 150 mm section of the chimney or liner. 

All joints in the connection between the stove and the chimney must be 
made gastight using fire cement and where necessary fire-proof rope infill. 
Means should be made for sweeping the entire length of the flue, be that 
through the appliance or by suitable sweeping hatch in the flue. 

Commissioning and handover

Ensure all parts are fitted in accordance with the instructions.

On completion of the installation allow a suitable period of time for any fire 
cement and mortar to dry out, before lighting the stove. Once the stove is 
under fire check all seals for soundness and check that the flue is functio-
ning correctly and that all products of combustion are vented safely to 
atmosphere via the chimney terminal.
On completion of the installation and commissioning ensure that the opera-
ting instructions for the stove are left with the customer. Ensure to advise 
the customer on the correct use of the appliance and warn them to use only 
the recommended fuel for the stove.
Advise the user what to do should smoke or fumes be emitted from the 
stove. The customer should be warned to use a fireguard to BS 8423:2002 
(Replaces BS 6539) in the presence of children, aged and/or infirm persons.

Содержание C i50

Страница 1: ...Ci50 Ci51 www contura eu Operation instructions...

Страница 2: ...e the window open for a few minutes until the fire has caught properly 1 Open the damper completely to max 2 The start up fire must consist of approx 11 pieces of kindling of varying dimensions with a...

Страница 3: ...op 3 The damper must be completely open until the logs turn black and catch fire This can take about 3 5 min The damper can then be closed The conditions for controlling combustion vary depending on t...

Страница 4: ...insulating properties It contains a certain amount of water that evaporates during the first lighting Whilst this happens combustion may seem to be slow and soot may build up on the insulation panels...

Страница 5: ...ustion is also poor layers of soot and tar build up in the chimney and could at worst lead to a chimney fire In addition it causes the glass of the insert to soot and may cause discomfort to those liv...

Страница 6: ...traight up The ash must be stored in a fireproof container with a lid for at least one week before being disposed of The grate and other cast iron components can be cleaned using a wirebrush It is imp...

Страница 7: ...installation of the carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufacturer s instructions Provision of an alarm must not be considered a substitute for either installi...

Страница 8: ...modate the weight of the stove and its chimney if the chimney is not independently supported The weight of the stove is indicated in the brochure The stove should preferably be installed on a non comb...

Страница 9: ...ns given under Warning Note above Air Controls Manually operated air control can be managed by adjusting the air control valve to increase decrease the air flow to the stove Use of fireguard When usin...

Страница 10: ...himney fires should not occur However if a chimney fire does occur turn off the stove immediately and isolate the mains electricity supply if applicable and tightly close the doors of the stove This s...

Страница 11: ...going Check that the combustion air damper is open fully Check that the ash box is not overfilled An overfilled ash box will block parts of the fireplace s air supply After sweeping the smoke outlet o...

Страница 12: ...to property and personal injury The ash pan must be emptied when it is full If this is not done the air supply can become blocked resulting in poor function In serious cases ash can find its way out t...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...E AB Box 134 285 23 Markaryd Sweden www contura eu Contura reserves the right to change dimensions and procedures described in these instructions at any time without special notice The current edition...

Отзывы: