CONTROL PANEL SPECIFIC CONFIGURATION 

The MVP-903 has been configured to accept a proprietary SPN signal to control speed over the 
CAN Bus inputs.  To reconfigure this module to accept a standard MPU speed signal, the speed 
selection in the Engine Parameters menu requires to be changed from J1939 to MPU.  

 

CONTROL PANEL SPECIFIC ALARMS AND SHUT DOWNS 

The panel has its own engine safety alarms and shut downs that can be enabled.  These alarms and 
shut downs are managed by the control panel.  The available options are listed below and can be 
accessed via the Engine Safety Configuration menu. 

Each alarm must be enabled in the Engine Safety Configuration menu to activate. 

Heading 

Default 

Range 

Units 

Sender Check Bypass 

0:10 

0:05 – 1:00 

Min:Sec 

Fuel Level Check 

Off 

Off / Always / Run 

 

Low Fuel Pre Alarm 

20 

0 - 100 

Low Fuel Alarm 

0 - 100 

Fuel Alarm Delay 

0:05 

0:01 – 1:40 

Sec 

Oil Pressure Check 

Run 

Off / Always / Run 

 

Low Oil Press Pre Alarm 

15 

0 - 100 

PSI 

Low Oil Press Alarm 

10 

0 - 100 

PSI 

Oil Press Alarm Delay 

0:05 

0:01 – 1:40 

Sec 

Temperature Check 

Run 

Off / Always / Run 

 

Low Temp Pre Alarm 

0 - 300 

Deg F 

Low Temp Alarm 

0 - 300 

Deg F 

High Temp Pre Alarm 

220 

150 - 300 

Deg F 

High Temp Alarm 

230 

150 - 300 

Deg F 

Temp Alarm Delay 

0:05 

0:01 – 1:40 

Min:Sec 

Battery Volts Check 

Off 

Off / Always / Run 

 

Low Battery Pre Alarm 

12.0 

0.0 – 40.0 

Volts 

Hi Battery Pre Alarm 

15.0 

0.0 – 40.0 

Volts 

Over Speed Check 

Off 

Off / Always / Run 

 

Over Speed Alarm 

3000 

650 - 5000 

RPM 

Over Speed Alarm Delay 

0:05 

0:01 – 1:40 

Min:Sec 

1) Off / Always / Run – Describes when the parameter will be monitored for alarm conditions.  Run 

refers to when the engine is running.  Off disables the alarm conditions.  Always enables the alarm 
constantly regardless of engine state. 

2) Alarm Delay – The time period, after Sender Check Bypass, that the parameter must be on the 

alarm condition before the alarm becomes latched. 

Содержание HARLO MVP-902

Страница 1: ...r MVP 902 Revision 2 0 ______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon...

Страница 2: ...ATION 2 MODULE CONNECTOR 4 CONTROL PANEL SPECIFIC CONFIGURATION 5 ENGINE ALARMS CODES AND MESSAGES 5 ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS CONTROL PANEL ANALOG AND DIGITAL INPUTS 7...

Страница 3: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 2 INSTALLATION INFORMATION...

Страница 4: ...T E M S S O L U T I O N S 3 MODULE CONNECTOR INFORMATION BATTERY CAN HIGH CAN LOW SPEED INPUT FUEL LEVEL INPUT BATTERY BATTERY AIR FILTER ALARM FLEX ANALOG 2 PARK BRAKE ACTIVE 4 WD ACTIVE FLEX ANALOG...

Страница 5: ...Fuel Pre Alarm 20 0 100 Low Fuel Alarm 1 0 100 Fuel Alarm Delay 0 05 0 01 1 40 Sec Oil Pressure Check Run Off Always Run Low Oil Press Pre Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Pres...

Страница 6: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 5 Indicator Lamps Engine Fault Lamp Engine Alarm Lamp...

Страница 7: ...Digital 4 Normally Open Open Closed B 3 Function Pre Alarm Message Park Brake Active Check Always Off Always Run Digital 5 Normally Open Open Closed B 4 Function Pre Alarm Message 4 WD Active Check Al...

Страница 8: ...wn is detected 11 Fuel Run Relay will be active during an engine start request and while the engine is running 12 Custom 1 Reserved for OEM applications 13 Preheat Relay will be active during programm...

Страница 9: ...croll menu options Press UP arrow button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up br...

Страница 10: ...l Unit Part View Control Unit Software Version View Controller Setup Quick Setup 1 PASSWORD PROTECTED Engine Parameter Configuration 2 Input Configuration 3 Throttle Configuration 4 Module Configurati...

Страница 11: ...Vernier TSC Mode Default Primary TSC Minimum Speed Default 800 RPM TSC Maximum Speed Default 2400 RPM TSC Bump Speed Default 20 RPM TSC Ramp Rate Default 100 RPM s Throttle Curve Default Linear Multl...

Страница 12: ...tus Transmit Default Off Panel Information Transmit Default Off Fault Transmit Default All Engine ID Auto Requirement Default No CAN Bus Monitor Default Off Text During Sleep Default Off Panel Request...

Отзывы: