CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
7
6)
Low Oil Press Alarm - Relay closes if a low oil pressure shutdown is detected.
7)
High Coolant Temp Alarm - Relay closes if a high engine temperature shutdown is detected.
8)
Over Speed Alarm - Relay closes if an over speed shutdown is detected.
9)
Over Crank Alarm - Relay closes if an over crank alarm is detected.
10)
Low Fuel Level Alarm - Relay closes if a low fuel level shutdown is detected.
11)
Fuel / Run - Relay will be active during an engine start request and while the engine is
running.
12)
Custom 1 - Reserved for OEM applications.
13)
Preheat - Relay will be active during programmed preheat period. Used to drive a preheat
relay.
Digital Function Activation
1) Off / Always / Run
– Describes when the parameter will be monitored for alarm conditions.
Run refers to when the engine is running. Off disables the alarm conditions. Always enables
the alarm constantly regardless of engine state.
2) Alarm Delay
– The time period, after Sender Check Bypass, that the parameter must be on
the alarm condition before the alarm becomes latched.