background image

 

CONTROLS, INCORPORATED 

C O N T R O L   S Y S T E M S   &   S O L U T I O N S  

 

 

 Main Menus 

 

Main Menus  

Sub Menus 

 

 

 

 

Operations Log 

View Last 32 Events (Start, Stop, Alarms) 

 

 

 

 

Alarms Event Log 

View Last 32 Alarms 

 

 

 

 

Module Information 

Control Unit Part# View 

 

 

Control Unit Software Version View 

 

 

 

 

Controller Setup 

Quick Setup 

(1) 

(PASSWORD PROTECTED)  Engine Parameter Configuration 

(2) 

 

Input Configuration 

(3) 

 

Throttle Configuration 

(4) 

 

Module Configuration 

(5) 

 

Display Configuration 

(6) 

 

CAN Configuration 

(7) 

 

Maintenance Configuration 

(8) 

 

Emissions Configuration 

(9) 

 

 

To access the controller setup menus, a password is required.  The password  

is 4345.

 

Configuration 
Menus 

Viewing Menus 

Содержание HARLO MVP-902

Страница 1: ...r MVP 902 Revision 2 0 ______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon...

Страница 2: ...ATION 2 MODULE CONNECTOR 4 CONTROL PANEL SPECIFIC CONFIGURATION 5 ENGINE ALARMS CODES AND MESSAGES 5 ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS CONTROL PANEL ANALOG AND DIGITAL INPUTS 7...

Страница 3: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 2 INSTALLATION INFORMATION...

Страница 4: ...T E M S S O L U T I O N S 3 MODULE CONNECTOR INFORMATION BATTERY CAN HIGH CAN LOW SPEED INPUT FUEL LEVEL INPUT BATTERY BATTERY AIR FILTER ALARM FLEX ANALOG 2 PARK BRAKE ACTIVE 4 WD ACTIVE FLEX ANALOG...

Страница 5: ...Fuel Pre Alarm 20 0 100 Low Fuel Alarm 1 0 100 Fuel Alarm Delay 0 05 0 01 1 40 Sec Oil Pressure Check Run Off Always Run Low Oil Press Pre Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Pres...

Страница 6: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 5 Indicator Lamps Engine Fault Lamp Engine Alarm Lamp...

Страница 7: ...Digital 4 Normally Open Open Closed B 3 Function Pre Alarm Message Park Brake Active Check Always Off Always Run Digital 5 Normally Open Open Closed B 4 Function Pre Alarm Message 4 WD Active Check Al...

Страница 8: ...wn is detected 11 Fuel Run Relay will be active during an engine start request and while the engine is running 12 Custom 1 Reserved for OEM applications 13 Preheat Relay will be active during programm...

Страница 9: ...croll menu options Press UP arrow button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up br...

Страница 10: ...l Unit Part View Control Unit Software Version View Controller Setup Quick Setup 1 PASSWORD PROTECTED Engine Parameter Configuration 2 Input Configuration 3 Throttle Configuration 4 Module Configurati...

Страница 11: ...Vernier TSC Mode Default Primary TSC Minimum Speed Default 800 RPM TSC Maximum Speed Default 2400 RPM TSC Bump Speed Default 20 RPM TSC Ramp Rate Default 100 RPM s Throttle Curve Default Linear Multl...

Страница 12: ...tus Transmit Default Off Panel Information Transmit Default Off Fault Transmit Default All Engine ID Auto Requirement Default No CAN Bus Monitor Default Off Text During Sleep Default Off Panel Request...

Отзывы: