Web Server and Setup Pages
WebRelay Users Manual
latch relay when input on (reset via web)
-
When a voltage is applied to the input, the relay
goes
on
. Once the relay is on it will stay
on
(unaffected by input changed) until it is turned
off
via
the web by a user or the WebRelay is powered off. This option is useful for alarming functions.
latch relay when input off (reset via web)
-
When a voltage is removed from the input, the
relay goes
on.
Once the relay is
on
it will stay
on
(unaffected by input changed) until it is turned
off via the web by a user or the WebRelay is powered off. This option is useful for alarming
functions.
latch relay when input changes (reset via web)
-
When a voltage is applied to the input or
removed from the input, the relay goes
on
. Once the relay is
on
it will stay
on
(unaffected by
input changes) until it is turned off via the web by a user or the WebRelay is powered off. This
option is useful for alarming functions.
toggle relay when input on
-
When a voltage is applied to the input, the relay will change
states. When a voltage is removed from the input, the relay will remain in its current state.
toggle relay when input off
-
When a voltage is removed from the input, the relay will change
states. When a voltage is applied to the input, the relay will remain in its current state.
toggle relay when input changes
-
When a voltage is applied to the input or removed from the
input the relay will change states.
pulse relay when input on
-
When a voltage is applied to the input, the relay will pulse for the
Pulse Duration specified. The voltage may remain on or be removed and the pulse time will not
be affected. If the voltage is applied, removed, and then re-applied before the end of the pulse
time, the Pulse Duration timer will be re-started (it will re-start each time a voltage is applied) and
the relay will continue to remain
on
until the timer expires.
pulse relay when input off
-
When a voltage is removed from the input, the relay will pulse for
the Pulse Duration specified. The voltage may remain off or be re-applied and the pulse time will
not be affected. If the voltage is removed, re-applied, and then removed again before the end of
the pulse time, the Pulse Duration timer will be re-started (it will re-start each time a voltage is
removed) and the relay will continue to remain
on
until the timer expires.
pulse relay when input changes
-
When a voltage is applied to or removed from the input, the
relay will pulse for the Pulse Duration specified. If the state of the voltage changes before the
end of the pulse, the timer will be re-started (it will re-start each time the voltage changes) and
the relay will continue to remain
on
until the timer expires.
Page 42
Xytronix Research & Design, Inc.