UD70
Issue code: 70nu2
6-10
Serial communications
The
UD70
will respond with a single control character, as follows:
Control Code
Meaning
ACK
Acknowledge — Message has been understood and implemented.
NAK
Message invalid, data is too long or out of range, parameter is invalid, parameter is
read-only, or the BCC is incorrect.
Example
Set parameter Pre-set frequency 1
Pre-set frequency 1 at +76.4 for Unidrive (unit 6, group 2) send:
Control
Address
Control
Parameter
Data
Control
BCC
EOT
2
2
6
6
STX
0
1
2
1
+
0
7
6
.
4
ETX
1
Re-writing data
Once a write message which includes the address field has been sent and
accepted with either a <
ACK
> or <
NAK
> response, subsequent write
messages to that particular
UD70
can use a re-write message structure in
which the address does not need to be re-transmitted. The re-write
structure is as follows:
STX
M1
M2
P1
P2
D1
...
Dn
ETX
BCC
When a different
UD70
is addressed, or an invalid character is received, the
re-write facility no longer functions. The first
UD70
can be addressed again
only by using the full write message with the address.
Calculating the block checksum (BCC)
The block checksum is calculated by applying an exclusive
OR
function to all
of the characters of a message after the
STX
control character.
XOR truth table
A
B
Out
0
0
0
0
1
1
1
0
1
1
1
0
For example, the serial command to set Pre-set speed 1
Pre-set speed 1 at
–34.5Hz on a Unidrive: