exception, code+65, rarely used (69..79)
configuration property fault (80)
exception, code not recognized (81)
BACnet client read/write timeout (82)
BACnet client received error response from slave (83)
SNMP client received no response from agent (84)
SNMP client unable to parse data (85)
SNMP client reply does not match request (86)
Out_Of_Service (81) (W)
BOOLEAN
COV_Increment (22) (W)
REAL (analog objects only)
Priority_Array (87)
BACnetPriorityArray (commandable objects only)
SEQUENCE SIZE (16) OF BACnetPriorityValue
REAL (each element, analog output objects)
ENUMERATED (each element, binary output objects)
Unsigned (each element, multi-state output objects)
Relinquish_Default (104)
(W)
REAL (analog objects)
ENUMERATED (binary objects)
Unsigned (multi-state objets)
Polarity (84)
BACnetPolarity (binary objects only)
ENUMERATED: normal(0)
Number_Of_States (74)
Unsigned (multi-state objects only)
Units (117)
BACnetEngineeringUnits (analog objects only)
14.2 Device Object Properties
The following properties are found in the Device object of the BB2-7010. In addition to standard Device
properties.
Property
Encoding
Object_Identifier (75)
BACnetObjectIdentifier
Object_Name (77)
CharacterString
Object_Type (79)
BACnetObjectType
ENUMERATED:
device (8)
System_Status (112)
BACnetDeviceStatus
Vendor_Name (121)
CharacterString
Vendor_Identifier (120)
Unsigned16
(should always return 208)
Model_Name (70)
CharacterString
Fimrware_Revision (44)
CharacterString
Application_Software_Version
(12)
CharacterString
Protocol_Version (98)
Unsigned
14. Object Properties
file:///C:/AAA_CSI/Literature/2015 User Guides/BB2-7010/BB2-7010 ...
2 of 3
10/16/2015 12:46 PM