The object name, units, value, and status are shown for the object number entered at the top of the page.
Click Prev/Next to scroll through the list. Click Refresh to update the page, or Update to accept changes.
The object name may be changed here. State text may be entered. When any of these are changed, be
sure to save the updated configuration by clicking Save on the Config File page under System Setup.
The destination of data for a Binary Output object will be writing the remote Modbus register via the map
indicated by the Device Link. The Modbus device will be updated upon change of source data and/or
periodically as defined by the Write Map.
The Binary Output object is commandable, meaning the BACnet client must write both a value and a
priority level for that value. The highest level value will be the one written to the Modbus register. If all
values are relinquished, the relinquish default value will be written to the Modbus register.
To set an output object manually from this page, check the Force box, enter a value in the Present Value
window, and select a priority level to assign to your forced value. Then click Update. To return a given
priority level to NULL, simply type the word NULL in the Present Value window, check Force, and click
Update.
Out of service means the Modbus register will not be written. Values written by the BACnet client will be
4. Using the BB2-7010 as a BACnet Server