Document Ref: DV40APP / Rev 2 09/02/2010
Page 16 of 23
Raised by GG Checked_ _JBJ
Note: The default levels are:
XP95 sensor
Discovery sensor
Default Alert level
45
45
Default Fire level
55
55
Valid Alert Levels
35, 40, 45, 50
35, 40, 45, 50
Valid fire levels
55, 60, 65, 70
55
Default sensitivity levels
N/A
3
Valid sensitivity levels
N/A
1, 2, 3, 4, 5
All ancillary devices have fixed responses except the Apollo Input Output module and the
Discovery Sounder/Beacon devices. The input for the Apollo Input Output module device
can be configured for response as a fire, fault, alert or indication only. The tone pair and
volume for the Discovery Sounder Beacon can be configured.
4.1.5 Discovery Device Functions
The following functions are available with Apollo Discovery devices:
Print drift compensation level by loop
Print device date of manufacture
Enable or disable LED pulsing mode
Configure Discovery Sounder/Beacon volume setting using magnetic wand
Configure Discovery Sounder/Beacon auto-stop function
4.1.6 Zone Allocation
The 96 Zone, 40 Character Discovery has 96 programmable zones. All loop devices can be
programmed into one of these zones through the engineers menu. Activation of a fire or a
fault on a device will cause operation of the fire or fault indicator associated with the zone.
The panel alphanumeric display will also indicate the zone number. The panel has an insert
fitted to the front door suitable for text descriptions of each zone location.
The engineer can also print out all the zones with the devices allocated to the zones.
4.1.7 Programmable Cause/Effect
Any loop device output can be individually programmed to operate in response to a common
event or a zone or group entering a specific condition.
The common events are: -
Common fire, output cleared on reset
Common fire, output cleared on silence alarms
Common alert, output cleared on reset
Common fault, output cleared on reset
Common indication, output cleared on reset
Alarms silenced
Panel reset
Evacuate (including remote evacuate)