Document Ref: DV40APP / Rev 2 09/02/2010
Page 13 of 23
Raised by GG Checked_ _JBJ
680R
680R
SWITCH
SWITCH
END OF LINE
3k9
INPUT CIRCUIT
INPUT CIRCUIT
Figure 1
– Input circuit configuration
3.6 Alarm circuits
The
96 Zone, 40 Character Discovery
panel has two alarm circuits, each rated at 1A. The
circuits are reverse polarity monitored for open and short circuit faults. To allow monitoring
all devices must be polarised To prevent damage to the control panel bells must also be
suppressed a bell fit diodes as shown in Figure 2. The circuit must be terminated with a 3k9
end of line resistor.
END OF LINE
3k9
POLARISING
DIODE (E.G. 1N4002S)
BELL
SOUNDER
SUPPRESSION
DIODE (E.G. 1N4002S)
ALARM C
ALARM CIRCUIT -
Figure 2
– Alarm circuit configuration
3.7 Mechanical and Environmental Specification
Size:
Height:
Width:
Depth:
480mm
410mm (2 loop and network repeater)
160mm including lock and indented holes
Weight excluding batteries:
15kg
Operating temperature:
-5ºC to 40ºC
Operating humidity:
5% to 95%
Electrical
Mains voltage:
230V AC +10%/-15%